FIGURE 5: 

MULTIPLE TRANSMITTER CONNECTIONS

Power Supply

       +    -

      +    -

      +    -

Temp.Transmitter #1

Temp.Transmitter #N

Temp.Transmitter #2

       -

VDC

+

 Controller

 

Gnd  In1 In2 In3

       = Connections
In1 = Controller Input #1
In2 = Controller Input #2
In3 = Controller Input #3

WIRING INSTRUCTIONS 

(Continued)

Note:  

All RTD’s are supplied with (2) or (3) flying lead 

wires. ACI’s transmitters are supplied with a 2 pole 
terminal block for RTD sensor connections. When wiring a 
3 wire RTD, connect the (2) common wires (same color) 
together into the same terminal block - see 

FIGURE 4

 

(right).

Formula for Number of Transmitters

Several transmitters may be powered from the same supply 
as shown in 

FIGURE 5 

(below). Each transmitter draws 

25mA; refer to the following equation to obtain the number 
of permissible transmitters: 

[# Transmitters] = [Current] / 

(25 mA)

.

FIGURE 4: 

3 WIRE RTD

3 WIRE RTD

SAME COLOR WIRES

RTD

TROUBLESHOOTING

TEMPERATURE PROBLEM

No Reading

No power to board - check voltage at power terminal - should be b8.5 and 32 VDC.

Reading too Low

RTD wires shorted. Disconnect wies from terminal block and check with ohmmeter. Reading should be close to 100 Ω or 1 KΩ. 

RTD Improper range of transmitter (too low). Check current or voltage - should be between 4-20 mA, 1-5 V, or 2-10 V.

Reading too High

RTD opened. Disconnect sensor wires from terminal block and check with ohmmeter. Reading should be close to 100 Ω or 1 KΩ.

Improper range of transmitter (too high). Check current or voltage - should be between 4-20 mA, 1-5 V, or 2-10 V.

Reading is Inaccurate

Sensor check:

 Disconnect sensor wires from terminal block and check with ohmmeter. Compare the resistance reading 

to the Temperature vs Resistance curves located on ACI’s website.

Transmitter check:

 Make sure sensor wires are connected to terminal block. Determine that the proper output is being 

transmitted based on predetermined span:

1. Go to ACI Website, Span to Output Page: http://www.workaci.com/content/span-output  
2. Enter the low end of the span
3. Enter the high end of the span
4. Click on the output of the transmitter. This will generate a span to output chart.
5. Measure output of transmitter.
6. Compare measured output to calculated output