Summary of Contents for DRN3.1

Page 1: ...al during operation However if the supply power is lost control of the circuit will revert back to the original controller signal An easy local override can be made by placing a fixed or variable resistor between W and R Fail safe terminals Jumper inputs can be specified to have the factory set them This will speed up installation time for the end user MOUNTING INSTRUCTIONS Circuit board may be mo...

Page 2: ... Point Signal Common To Failback Control Wiper Maximum Minumum Test Points for Resistance Card See Page 4 Wiper Maximum Minimum To Actuator Optional Offset Pots for Resistive Network High Low Wiper 24 VAC Power Supply or VDC Pulsed Dry Contact Figure 2 Non Isolated PWM Signal Input For switching common see wiring diagram on page 2 NOTE Please follow Minimum Maximum and Wiper designators as shown i...

Page 3: ...c Floating Pt 240 sec Floating Pt S1 S2 S3 S4 S5 S6 JUMPER SETTINGS PULSE FLOATING POINT Version 2 Chip 0054y0b hex Input 0 1 10 sec pulse S1 S2 S3 S4 S5 S6 JUMPER SETTINGS DUTY CYCLE PULSE Version 4 Chip 0305y1a hex RESISTOR NETWORK Each DRN3 1 requires a plug in resistor network card RN to operate properly This resistance card determines the simulated slide wire potentiometer values for the outp...

Page 4: ...ge is not present remove the or positive wire and measure from wire to 24V If no voltage is measured check the wiring from controller If voltage disappears or is reduced when connected to the DRN3 1 confirm input jumper is set to voltage mode and remove signal input wires and power from unit Measure the resistance from 24V to V I Resistance in the voltage modes will be around 10K If input is short...

Page 5: ...twork and will increase proportionally to the commanded input value To reverse the output signal measure resistance from Wiper to Maximum terminal blocks This will begin at the maximum signal as specified by your resistor network and will decrease proportionally to the commanded input value A clicking sound will occur when resistance is changed Resistance changes in steps and is divided into 256 e...

Page 6: ...120 240s 5 24 VDC VAC 750Ω nominal See Resistance Network Ordering Grid Form C Relays 256 Steps No wrap around 2A 24 VDC 0 5A 240 VAC 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C RoHS2 WEEE NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Range Im...

Page 7: ...NOTES Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 6 0 I0000475 ...

Page 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 6 0 I0000475 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com ...