aci DRN3.1 Installation & Operation Instructions Download Page 4

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 6.0

I0000475

SETTING THE JUMPERS

Remove power from the DRN3.1.  Place jumpers S1 through S6 in the appropriate positions.  All six 
jumpers must be in proper position for each input type.  Hold the DRN3.1 vertical with the label at top 
right to orient its jumper shunts with the chart.  Version #1 and Version #2 share the same analog inputs.  
Ramping time for floating point inputs are selectable.  

SETTING THE JUMPERS 

(Continued)

Version #4 accepts a continuous pulse signal command string within a 10 second window.  No pulse in this 
10 second window produces minimum percent output.  A ten second pulse in this 10 second window 
produces 100% output.  Continuous pulse will produce maximum percent output.

When power is restored, changes will be recognized.  Apply 24 VAC/VDC to “PWR” terminal, confirm power 
light is on and measure voltage to confirm proper voltage.

When power is applied to terminals “+24V” and “-“, the POWER LED will light and the Fail Safe terminals will 
be disconnected from the output terminals.  Fail-back only occurs when the DRN3.1 has lost power.  When 
the DRN3.1 is not powered on terminals “24V” and “-“, the Fail Safe terminals are connected to the Output 
terminals.  Check for continuity.

The DRN3.1 will automatically fail-back to 0 Ohms.  For a fail-back to some other resistance, a manual 
potentiometer or fixed resistor can be added between Minimum and Wiper only, if outputting a normal 
acting signal.  If outputting a reverse acting signal, please contact ACI for assistance.

TESTING THE INPUT

Voltage input

Connect the “+” or positive wire to “V/I+”.  Connect the common to “24V-“.  Apply a voltage from control 
source.  Measure voltage at “24V-“ and “V/I+” at terminal block. If the commanded voltage is not present, 
remove the “+” or positive wire and measure from “+” wire to   “24V-“.  If no voltage is measured check the 
wiring from controller.  If voltage disappears or is reduced when connected to the DRN3.1, confirm input 
jumper is set to voltage mode and remove signal input wires and power from unit.  Measure the resistance 
from “24V-“ to “V/I+”.  Resistance in the voltage modes will be around 10K.  If input is shorted, contact ACI 
Technical Support.  If not shorted, remove the controller input common and connect 24 VDC/VAC to the 
DRN3.1.  Check for ground loop:  Place meter in voltage mode and measure VAC and VDC from analog 
input common wire to power supply common.  If any voltage is measured in DC or AC a ground loop most 
likely exists.  Check power commons and / or ground potentials.   Use a separate 24 volt transformer for the 
DRN3.1 and let common float.

Current input

Confirm the input jumper is in the correct position.  Measured input resistance should be around 250 
Ohms.  Connect “+” or positive to “V/I+” and common or “-“ to “24V-“.  Apply mA signal.  Place meter in 
voltage and measure voltage across “V/I+” and “24V-“ 4 mA is equal to 1 volt and 20 mA is equal to 5 volts.  
Use Ohms Law to find voltage from current.  (Current x 250 = Volts. Example: 12 mA or 0.012 x 250 = 3 
volts).  If no voltage is present, check wiring for open.  Current cannot exist without voltage present from 
“V/I+” to “24V-“ unless dead shorted.

Pulse Width Modulated (or PWM) input

Apply 24 VAC/VDC to the PWR terminals.  Connect your meter to the Wiper and Maximum terminals on the 
output terminal block.  Set meter to resistance range of resistor network.  Connect a jumper wire from UP 
to the 24V “+” terminal (this is your jumper wire #1).  Connect another jumper wire into the 24V “-“ terminal 
only (this is your jumper wire #2).  You are now ready to simulate a timed pulse signal.  For testing 
purposes, select 0.1 to 25.5 or 0.1 to 10 seconds on version 2.  Be sure to reset power to allow the DRN3.1 
to recognize new settings.  Take the free end of jumper wire #2 and connect by holding wire to 

Summary of Contents for DRN3.1

Page 1: ...al during operation However if the supply power is lost control of the circuit will revert back to the original controller signal An easy local override can be made by placing a fixed or variable resistor between W and R Fail safe terminals Jumper inputs can be specified to have the factory set them This will speed up installation time for the end user MOUNTING INSTRUCTIONS Circuit board may be mo...

Page 2: ... Point Signal Common To Failback Control Wiper Maximum Minumum Test Points for Resistance Card See Page 4 Wiper Maximum Minimum To Actuator Optional Offset Pots for Resistive Network High Low Wiper 24 VAC Power Supply or VDC Pulsed Dry Contact Figure 2 Non Isolated PWM Signal Input For switching common see wiring diagram on page 2 NOTE Please follow Minimum Maximum and Wiper designators as shown i...

Page 3: ...c Floating Pt 240 sec Floating Pt S1 S2 S3 S4 S5 S6 JUMPER SETTINGS PULSE FLOATING POINT Version 2 Chip 0054y0b hex Input 0 1 10 sec pulse S1 S2 S3 S4 S5 S6 JUMPER SETTINGS DUTY CYCLE PULSE Version 4 Chip 0305y1a hex RESISTOR NETWORK Each DRN3 1 requires a plug in resistor network card RN to operate properly This resistance card determines the simulated slide wire potentiometer values for the outp...

Page 4: ...ge is not present remove the or positive wire and measure from wire to 24V If no voltage is measured check the wiring from controller If voltage disappears or is reduced when connected to the DRN3 1 confirm input jumper is set to voltage mode and remove signal input wires and power from unit Measure the resistance from 24V to V I Resistance in the voltage modes will be around 10K If input is short...

Page 5: ...twork and will increase proportionally to the commanded input value To reverse the output signal measure resistance from Wiper to Maximum terminal blocks This will begin at the maximum signal as specified by your resistor network and will decrease proportionally to the commanded input value A clicking sound will occur when resistance is changed Resistance changes in steps and is divided into 256 e...

Page 6: ...120 240s 5 24 VDC VAC 750Ω nominal See Resistance Network Ordering Grid Form C Relays 256 Steps No wrap around 2A 24 VDC 0 5A 240 VAC 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C RoHS2 WEEE NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Range Im...

Page 7: ...NOTES Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 7 Version 6 0 I0000475 ...

Page 8: ...nc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 6 0 I0000475 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com ...

Reviews: