Always reads a string value of "-123.45" (Null terminated). For
testing proper communication and interpretation of values.
Non-null terminated character string of the Serial Number. For
example, "12345678”
Non-null terminated character string of the Firmware Version. For
example, "02.00.000.90"
Test String Test Value
Serial Number
Firmware Version
9002 Thru
9005
9006 Thru
9009
9010 Thru
9015
INPUT REGISTER (IR)
2001
2002
2003
2004
9001
9002
Temperature range Minimum value (Tenths). Signed Integer.
Temperature range Maximum value (Tenths). Signed Integer.
Relative Humidity range Minimum value (Tenths)
Relative Humidity range Maximum value (Tenths)
Always reads a value of 54321. For testing proper communication
and interpretation of values.
Always reads a value of -12345. For testing proper communication
and interpretation of values.
Temperature Range
Min
Temperature Range
Max
RH Range Min
RH Range Max
Unsigned Integer
Test Value
Signed Integer Test
2000
2001
2002
2003
9000
9001
HOLDING REGISTER (HR)
1
Value - Units:
62 - Degrees Celsius
63 - Degrees Kelvin
64 - Degrees Fahrenheit
Temperature Units
0
2
3
1001
1002
9001 Thru
9016
9017 Thru
9048
9049 Thru
9080
Temperature Offset Value (Tenths) Signed Integer.
User can set an offset that will be added to Temperature sensor and
reflected in IR3. Range of -5.0 to 5.0 degrees Celsius/degrees Kelvin
(-9.0 to 9.0 degrees Fahrenheit).
For example, writing -16 would add an offset of -1.6 degrees.
Relative Humidity Offset (Tenths)
User can set an offset that will be added to RH sensor and reflected
in IR4. Range of -10.0 to 10.0 %RH.
For example, writing -16 would add an offset of -1.6 %RH.
User can set what temperature value (Tenths) that would be
returned when reading IR3 and Test Mode is Enabled in CL1001. For
Example -400 would be -40.0.
User can set what RH value (Tenths) that would be returned when
reading IR4 and Test Mode is Enabled in CL1001.
Device Name, Device Location, and Device Description are user
settable character strings (Null terminated) that can be used to allow
for system customization and device identification.
For example:
Device Name (Modbus 9001 thru 9016) could be set to a system ID:
"S2253"
Device Location (Modbus 9017 thru 9048) could be set to:
"Building 5, Floor 2, Duct 3"
Device Description (Modbus 9049 thru 9080) could be set to:
"Cold air return sensor"
Temperature Offset
Value
RH Offset Value
Test Mode
Temperature Value
Test Mode RH Value
Device Name
Device Location
Device Description
1
2
1000
1001
9000 Thru
9015
9016 Thru
9047
9048 Thru
9079