background image

Page 6

PAR 2

0
0
1
1

PAR 1

0
1
0
1

Mode (Databits-Parity-Stop Bits)

8-Even-1
8-Odd-1
8-None-2
8-None-1 (Non-Standard)

TABLE 6: 

PARITY AND STOP BITS

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

1001

0 = Disable Test Mode. IR3 and IR4 will read with current Sensor 

Value.

1 = Enable Test Mode. IR3 and IR4 will read with the values stored 

in HR1001 and HR1002 .

Test Mode Enable

1000

REFERENCE

DESCRIPTION

NAME

ADDRESS

1

2
3

4

For each bit location:
0 = Sensor not present
1 = Sensor present
 
Bit 0 - Temperature Sensor
Bit 1 - RH sensor
N/A
For example, a value of 312 would represent 31.2 Degrees of the 
units selected in HR1.  Signed Integer.
For Example: A value of 429 would represent 42.9% Relative 
Humidity.

Sensors Present

Reserved
Temperature Sensor 
Value
RH Sensor Value

0

1
2

3

MODBUS RTU MAP

DEVICE CONFIGURATION THROUGH MODBUS RTU

MODBUS RTU DATABITS, PARITY, AND STOP BITS SELECTION

Confirm Modbus Protocol is selected via dipswitch #4 on SW4 - see

 FIGURE 4

. The device that requests 

information is called the Modbus Master and the devices giving the information are Modbus Slaves.  The 
Modbus sensors are slave devices and the number of Data Bits needs to be the same as in the Master 
device configuration. ACI’s Modbus RTU sensors utilize 8 data bits during communication exchange.

Parity and stop bit selection is performed via the SW4 switch located on the board.  Dipswtiches #1 and #2 
are adjusted to select the parity and stop bits - see 

TABLE 6

. Where (0) is OFF and (1) is ON. If BACnet 

protocol is selected these dipswitches are irrelevant.  

TEST MODE Modbus RTU

There are 5 data values in test mode.  Coil 1001, 
Holding Registers (HR) 1001 and 1002, and the 
Input Registers (IR) 0003 and 0004 for Temp and 
RH values.  When Coil 1001 is enabled, reading IR 
0003 and 0004 will respond with the values in HR 
1001 and 1002, other wise they will respond with 
the actual sensor values.  General process for this 
is to write initial test values to HR 1001 and 1002, 
Enable Coil 1001 and then read as normal from IR 
0003 and 0004.  While Coil 1001 is enable, it is 
possible to write a change of value to IR 1001 and 
1002, which will be reflected in the next read from 
IR 0003 and 0004.  When testing completed, 
disable Coil 1001.  The status of Coil 1001 and HR 
1001 and 1002 are not persistent between 
reset/power cycle.

MODBUS RTU MODEL

Modbus data model: 
Four (4) primary data tables (addressable registers) 
• Discrete Input (read only bit). 
• Coil (read / write bit). 
• Input register (read only 16 bit word, 

interpretation is up to application). 

• Holding register (read / write 16 bit word). 

INPUT REGISTER (IR)

Version: 2.0

I0000927

COILS (CL)

Summary of Contents for BACnet Series

Page 1: ...we recommend removing the block wiring and reattaching before mounting 16 to 22 AWG two conductor shielded cable is recommended for powering the sensors ACI recommends using Belden 3105 or compatible cable for RS 485 communication wiring This wire has 120 ohm input impendence The terminal blocks allow for 1 or 2 wires to be connected in each position for daisy chaining Daisy chain the RS 485 wirin...

Page 2: ...ings followthesetips The sensor should be mounted in the middle of the duct where air circulation is well mixed no stratification and not blocked by obstructions Stratification and obstructions can cause sensing errors An example is downstream from a heating or coolingcoil Duct probe should be placed 3 to 4 duct segments down from any bend or obstructions and away from 90 bends Mount the sensor on...

Page 3: ...es are allowed to send and receive tokens on the MSTP network ACI s Modbus RTU sensors are slave devices Only one master is connected to the bus and several slave nodes are connected to the same trunk The Master initiates communication The slave nodes only respond to a request from the Master Slave nodes do not communicate with each other Each branch must have all devices connected with connected ...

Page 4: ... INFORMATION One LED indicates four statuses Solid green shows that power is good but no data is transmitting A solid Amber indicates that auto baud is set and no data has been received to set a baud rate Green Amber flashing indicates data is being transmitted or received Solid Red LED status indicates an error state usually loss of communication on the network If BACnet is the selected protocol ...

Page 5: ...Sensor objects AI0 and AI1 a test mode can be set by writing the Boolean value true to the out of service property Then the present value can be set to any valid test value the user requires This allows a user to test reactions to specific values returned by this device DEVICE LOCATION The device location is optional but is intended to allow for further definition of the device s location The devi...

Page 6: ...e as in the Master device configuration ACI s Modbus RTU sensors utilize 8 data bits during communication exchange Parity and stop bit selection is performed via the SW4 switch located on the board Dipswtiches 1 and 2 are adjusted to select the parity and stop bits see TABLE 6 Where 0 is OFF and 1 is ON If BACnet protocol is selected these dipswitches are irrelevant TEST MODE Modbus RTU There are ...

Page 7: ...ature Units 0 2 3 1001 1002 9001 Thru 9016 9017 Thru 9048 9049 Thru 9080 Temperature Offset Value Tenths Signed Integer User can set an offset that will be added to Temperature sensor and reflected in IR3 Range of 5 0 to 5 0 degrees Celsius degrees Kelvin 9 0 to 9 0 degrees Fahrenheit For example writing 16 would add an offset of 1 6 degrees Relative Humidity Offset Tenths User can set an offset t...

Page 8: ...able 4 seconds BACnet MS TP or Modbus RTU Field Selectable EIA RS 485 0 to 127 0 Default Must be changed if Modbus RTU is selected protocol Field Selectable Auto Baud Default BACnet Only 9600 19200 38400 57600 76800 115200 Field Selectable 1035000 Address example Address 127 1035127 Field Configurable None Even Odd Field Selectable 1 or 2 Field Selectable 8 Screw Terminal Blocks 16 AWG 1 31 mm2 to...

Reviews: