PRODUCT SPECIFICATIONS
12 to 36 VDC / 24 VAC +/- 10%, 50/60 Hz (Reverse Polarity Protected)
25 mA maximum (0.67 VA)
-22 to 176°F (-30 to 80°C)
-40 to 302°F (-40 to 150°C )
@ 77°F (25°C):
+/- 1.0°F (+/- 0.5°C)
+/- 9°F (+/- 5°C) (Field Configurable)
BACnet MS/TP or Modbus RTU = Field Selectable; EIA RS-485
0 to 127 (0 (Default - Must be changed if Modbus RTU is selected protocol);
Field Selectable)
Auto Baud (Default,
BACnet Only
), 9600, 19200, 38400, 57600, 76800, 115200
(Field Selectable)
1 Address (example: Address 127 = 1035127; Field Configurable)
None/Even/Odd = Field Selectable
1 or 2 = Field Selectable
8
Screw Terminal Blocks / 16 AWG (1.31 mm
2
) to 22 AWG (0.33 mm
2
)
0.45 lbf-in (0.5 Nm) nominal
½” NPS (National Pipe Straight) Male Thread
“-PB” Enclosure:
ABS Plastic, UL94-HB, Plenum Rated
Supply Voltage:
Current Consumption:
Operating Temperature Ranges
Transmitter:
Sensor:
Temperature Measurement Accuracy:
Temperature Calibration Offset:
Communication Protocol:
Sensor Addresses:
Supported Baud Rates:
Device Instance Number:
Parity (Modbus RTU)
Stop Bits (Modbus RTU)
Databits (Modbus RTU)
Connections / Wire Size:
Terminal Block Torque Rating:
Thermowell Instrument:
Enclosure Specifications:
Page 8
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone:
1-888-967-5224 |
Website:
workaci.com
1001
1002
9001 Thru
9016
9017 Thru
9048
9049 Thru
9080
User can set what temperature value (Tenths) that would be
returned when reading IR3 and Test Mode is Enabled in CL1001. For
Example -400 would be -40.0.
User can set what RH value (Tenths) that would be returned when
reading IR4 and Test Mode is Enabled in CL1001.
Device Name, Device Location, and Device Description are user
settable character strings (Null terminated) that can be used to allow
for system customization and device identification.
For example:
Device Name (Modbus 9001 thru 9016) could be set to a system ID:
"S2253"
Device Location (Modbus 9017 thru 9048) could be set to:
"Building 5, Floor 2, Duct 3"
Device Description (Modbus 9049 thru 9080) could be set to:
"Cold air return sensor"
Test Mode
Temperature Value
Test Mode RH Value
Device Name
Device Location
Device Description
1000
1001
9000 Thru
9015
9016 Thru
9047
9048 Thru
9079
Version: 2.0
I0000929
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE
Standard 135 is the responsibility of BACnet International (BI). BTL is a registered trademark of BACnet International.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.