TEMPERATURE AND RH OFFSET

This device allows for a temperature offset of +/-5C (9F) and an RH offset of +/-10%. By default, these 
values are set to 0, meaning no offset is added.

These are set by writing to the present value of the Temperature Calibration Offset (AV0) or RH Calibration 
Offset (AV1). The value written must be within the specified range or an error will be returned. To set back 
to factory settings, write any changed values to 0.

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 6

TEMPERATURE UNITS CONFIGURATION

For temperature, the units of measure can be configured using 
BACnet. By writing to the units property of the temperature sensor 
(AI0), the reported temperature units can be changed. 

TABLE 5 

shows the values to write.

PAR 2

0
0
1
1

PAR 1

0
1
0
1

Mode (Databits-Parity-Stop Bits)

8-Even-1
8-Odd-1
8-None-2
8-None-1 (Non-Standard)

TABLE 7: 

PARITY AND STOP BITS

Note: The table shows all objects for Temperature and RH. If you have a Temperature only model, the RH objects(AI-1 and 
AV-1) will not be present. If you have a RH only model, the Temperature objects (AI-0 and AV-0) will not be present.

TABLE 5: 

UNIT SETTING

UNITS

°F
K
°C

VALUE

64
63
62

OBJECT TYPE

Device
Analog 
Inputs
Analog 
Values

BACnet ENGINEERING UNITS

- - - - - - - - - - - - - - - - - - - - - - - - - - 
degrees-Fahrenheit (64) - default
percent-relative-humidity (29)
delta-degrees-Fahrenheit (120)

percent-relative-humidity (29)

PIC STATEMENT QR

RANGE

0-4194302
34.7 - 122.0
0.0 - 95.0
-9.0 - 9.0

-10.0 -10.0

OBJECT NAME

BN211x0
Temperature Sensor
RH Sensor
Temperature 
Calibration Offset
RH Calibration Offset

OBJECT ID

- - - - - - - - - - 
AI-0
AI-1
AV-0

AV-1

TABLE 6: 

BACnet OBJECT TABLE

DEVICE CONFIGURATION THROUGH MODBUS RTU

MODBUS RTU DATABITS, 

PARITY, AND STOP BITS 

SELECTION

Confirm Modbus Protocol is selected via 
dipswitch #4 on SW4 - see

 FIGURE 8 (P.4)

. The 

device that requests information is called the 
Modbus Master and the devices giving the 
information are Modbus Slaves.  The Modbus 
sensors are slave devices and the number of Data 
Bits needs to be the same as in the Master device 
configuration. ACI’s Modbus RTU sensors utilize 8 
data bits during communication exchange.

Parity and stop bit selection is performed via the 
SW4 switch located on the board.  Dipswtiches #1 
and #2 are adjusted to select the parity and stop 

bits -  see 

TABLE 7

. Where (0) is OFF and (1) is ON. 

If BACnet protocol is selected these dipswitches 
are irrelevant.  

TEST MODE Modbus RTU

There are 5 data values in test mode.  Coil 1001, 
Holding Registers (HR) 1001 and 1002, and the 
Input Registers (IR) 0003 and 0004 for Temp and 
RH values.  When Coil 1001 is enabled, reading IR 
0003 and 0004 will respond with the values in HR 
1001 and 1002, other wise they will respond with 
the actual sensor values.  General process for this 
is to write initial test values to HR 1001 and 1002, 
Enable Coil 1001 and then read as normal from IR 
0003 and 0004.  While Coil 1001 is enable, it is 
possible to write a change of value to IR 1001 and 
1002, which will be reflected in the next read from 
IR 0003 and 0004.  When testing completed, 
disable Coil 1001.  The status of Coil 1001 and HR 
1001 and 1002 are not persistent between 
reset/power cycle.

Version: 2.0

I0000929

Summary of Contents for BACnet / Modbus IMMERSION Series

Page 1: ...tor shielded cable is recommended for powering the sensors ACI recommends using Belden 3105 or compatible cable for RS 485 communication wiring This wire has 120 ohm input impendence The terminal bloc...

Page 2: ...no stratification Reference FIGURE 4 Make sure the entire thermowell is immersed If the thermowell is longer than the pipe diameter the thermowell should be installed in an elbow or Tee Apply thermal...

Page 3: ...NPS process thread to be used with a machined thermowell or previously installed thermowell Verify the existing thermowell insertion length of the pipe is suitable for your selected Immersion If the...

Page 4: ...a line When the jumper is set to DIS disable the resistance is not added By default the jumper is placed in the DIS disabled position SW4 OFF ON 1 ON 2 3 4 BACnet MS TP and Modbus RTU INTERFACE Contin...

Page 5: ...when a change is made the device must be power cycled or reset for changes in address to be made DEVICE CONFIGURATION THROUGH BACnet DEVICE INSTANCE The Device Instance by default is 1035000 plus the...

Page 6: ...NAME BN211x0 Temperature Sensor RH Sensor Temperature Calibration Offset RH Calibration Offset OBJECT ID AI 0 AI 1 AV 0 AV 1 TABLE 6 BACnet OBJECT TABLE DEVICE CONFIGURATION THROUGH MODBUS RTU MODBUS...

Page 7: ...tring of the Firmware Version For example 02 00 000 90 Sensors Present Reserved Temperature Sensor Value RH Sensor Value Temperature Range Min Temperature Range Max RH Range Min RH Range Max Unsigned...

Page 8: ...ite workaci com 1001 1002 9001 Thru 9016 9017 Thru 9048 9049 Thru 9080 User can set what temperature value Tenths that would be returned when reading IR3 and Test Mode is Enabled in CL1001 For Example...

Reviews: