Duct Mount 

 

 

 

 

 

 

Panel Mount 

 

Figure 5: DLP Mounting

 

WIRING 
Shielded is recommended cable with 16 to 24AWG conductors

. The hinged cover must be opened to connect wires to the unit’s 

finger push-button terminal blocks. Each DLP unit can be configured to three output signals: 4-20mA, 0-5V or 0-10V.  Use the Wiring 
Connections 

(Table 1)

 and diagrams 

(Figure 7)

 to determine the proper wiring for your application.  See 

Table 1

 for Output Mode 

and Output Signal switch positions.     

Output Signal 

Output Mode 

Output Signal 

Supply Voltage

Wire Connections 

  

(SW1) 

(SW3 Position 4)

  

Red Black  White  Yellow

0-5 VDC 

Vout 

5V 

VAC/VDC 

V+ 

COM  VOUT

n/c 

0-10 VDC 

Vout 

10V 

VAC/VDC 

V+ 

COM  VOUT

n/c 

4-20 mA 

mA 

n/a 

VDC 

V+ 

n/c  

n/c 

IOUT 

n/a=Not Applicable 

  

Table 1: Wiring Connections 

  

  

  

  

n/c=No Connection 

 

Figure 6: SW1 and SW3 Output Switches

 