AUTOMATION COMPONENTS, INC
Version : 5.0
2305 Pleasant View Road
I0000777
Middleton, Wisconsin 53562
Page 3 of 6
www.workaci.com
(888) 967-5224
Duct Mount
Panel Mount
Figure 5: DLP Mounting
WIRING
Shielded is recommended cable with 16 to 24AWG conductors
. The hinged cover must be opened to connect wires to the unit’s
finger push-button terminal blocks. Each DLP unit can be configured to three output signals: 4-20mA, 0-5V or 0-10V. Use the Wiring
Connections
(Table 1)
and diagrams
(Figure 7)
to determine the proper wiring for your application. See
Table 1
for Output Mode
and Output Signal switch positions.
Output Signal
Output Mode
Output Signal
Supply Voltage
Wire Connections
(SW1)
(SW3 Position 4)
Red Black White Yellow
0-5 VDC
Vout
5V
VAC/VDC
V+
COM VOUT
n/c
0-10 VDC
Vout
10V
VAC/VDC
V+
COM VOUT
n/c
4-20 mA
mA
n/a
VDC
V+
n/c
n/c
IOUT
n/a=Not Applicable
Table 1: Wiring Connections
n/c=No Connection
Figure 6: SW1 and SW3 Output Switches