 Troubleshooting 

 

Problem

 

Solution

 

Current switch didn’t activate (Test # 1) 

Disconnect the wires from the current switch output.  Measure the 
resistance across the contacts with an Ohmmeter.  

See Figure 7

 below 

for resistance readings for a good unit. 

Current switch didn’t activate (Test # 2) 
 

Verify that the current flowing in the conductor being monitored is 
above the fixed trip point as listed in the operating specifications.  If the 
sensor is monitoring less than the fixed trip point 

See Figure 3

 on Page 

1. 

 
 

ACI Model # 

Resistance if switch open 

Resistance if switch closed 

A/MCS 

Greater than 1 Meg ohms 

Approximately 0.2 ohms 

A/MSCS 

Greater than 1 Meg ohms 

Approximately 0.2 ohms 

Figure 7 

 
 