Troubleshooting
Problem
Solution
Current switch didn’t activate (Test # 1)
Disconnect the wires from the current switch output. Measure the
resistance across the contacts with an Ohmmeter.
See Figure 7
below
for resistance readings for a good unit.
Current switch didn’t activate (Test # 2)
Verify that the current flowing in the conductor being monitored is
above the fixed trip point as listed in the operating specifications. If the
sensor is monitoring less than the fixed trip point
See Figure 3
on Page
1.
ACI Model #
Resistance if switch open
Resistance if switch closed
A/MCS
Greater than 1 Meg ohms
Approximately 0.2 ohms
A/MSCS
Greater than 1 Meg ohms
Approximately 0.2 ohms
Figure 7
WEEE Directive
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of
with household waste. Do not burn.
LISTED
3SR0
C