aci A/CS2 Installation And Operation Instructions Download Page 3

AUTOMATION COMPONENTS, INC                                                                                                                                                                                 Version : 3.0 

                                                  Page 3 of 3                                                                                              I0000787     

                                                                                                  

 

 

Figure 5: Analog Circuit 

 

 Troubleshooting 

 

Problem

 

Solution

 

LED is on but the current switch didn’t activate  Disconnect the wires from the current switch output.  Measure the resistance 

across the contacts with an Ohmmeter.  

See Figure 6

 for the actual resistance 

readings for an open or closed switch reading. 

LED didn’t turn on and the current switch 

didn’t activate 

 

Verify that the current flowing in the conductor being monitored is above the 

fixed trip point as listed in the operating specifications.  If the sensor is 

monitoring less than the fixed trip point 

See Figure 3

LED not on but the Current Switch is Activated  LED not indicating correctly, may have been damaged 

Current Switch is operating at a low-level 

current or failing to operate within the accuracy 

specifications. 

For A/SCS2 Series, visually check the mating parts of the core to ensure there is 

no debris between the split contacts. Remove all debris or dust manually and 

close the current sensor,

 See Figure 2

. Retest the sensor in your application.  

 

ACI Model #  Fixed Trip Point  Resistance if switch open  Resistance if switch closed 

A/CS2 

0.25 Amps 

Greater than 1 Meg ohms 

Less than 10 ohms 

A/CSX2 

0.25 Amps 

Greater than 1 Meg ohms 

Less than 10 ohms 

A/SCS2 

1.5 Amps 

Greater than 1 Meg ohms 

Less than 10 ohms 

A/SCS2-L 

0.5 Amps 

Greater than 1 Meg ohms 

Less than 10 ohms 

A/SCSX2 

1.5 Amps 

Greater than 1 Meg ohms 

Less than 10 ohms 

 

              

 

 

 Figure 6 

 

 WEEE Directive 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling center.  Do not dispose of 

with household waste.  Do not burn. 

 

 