aci A/CS2 Installation And Operation Instructions Download Page 2

AUTOMATION COMPONENTS, INC                                                                                                                                                                                 Version : 3.0 

                                  Page 2 of 3                                                                                              I0000787     

                                                                                  

 LED 

The Red LED will indicate whether the current is above (LED On) or below (LED Off) the fixed trip point.  At very low 

monitored input currents the Red LED may not light to indicate the current is above the trip point. 

 

Application Notes  

The conductor being monitored may be looped through the sensor multiple times.  The loops increase the current measured by the 

current switch.  

Each time the conductor passes through the current switch window equals one loop 

(See Figure 3 below)

.  

To 

determine the proper number of loops required, take the rated Fixed Trip Point (see Figure 6) of the current switch and divide it by 

the Operating Current of the Monitored Device, add one (1), then round up to the nearest whole number.  Example: When using 

the A/CS2, a small fan operating at 0.1A should be wrapped through the sensor four times to give you a total operating current of 

0.4 Amps flowing through the A/CS2.  Formula Example: (0.25A/0.1A) = 2.5 + 1 = 3.5

, which rounded up equals 4 loops. 

 

      One Loop   

 

 

 

    Four Loops 

 

Figure 3: Wires Through Sensors 

 Wiring 

ACI recommends the use of a two conductor 16 to 22 AWG shielded cable or twisted pair 

copper wire only,

 for all current switch 

applications.  A maximum wire length of less than 30 meters (98.4 feet) should be used between the current switch and the 

Building Management System or controller.  

Note:

  

When using a shielded cable, be sure to connect only (1) end of the shield to 

ground at the controller.  Connecting both ends of the shield to ground may cause a ground loop.  

When removing the shield 

from the sensor end, make sure to properly trim the shield to prevent any chance of shorting.  The current switch output terminals 

represent a solid-state switch for controlling both AC and DC loads and are not polarity sensitive.  Tighten the screws at the 

terminal block connections to the recommended torque of 0.5 to 0.6 Nm (4.43 to 5.31 in-lbs.).  The aperture (hole) size of the 

current switch is 0.75” (1.90 cm). 

 Application Examples 

See 

Figure 4

 and 

Figure 5

 for two different current switch applications using your Building Management System (DDC/PLC 

Controller).  

Figure 4

 is showing the use of the Go/No Go Current Switch as a Digital Input to your DDC Controller, whereas 

Figure 5

 is showing you how to use the Go/No/Go Current Switch in conjunction with your building management system to  

control a fan or pump for example. 

 

 

 

 

Figure 4: Digital Circuit 

 