aci A/ASCS Installation And Operation Instructions Download Page 3

2305 Pleasant View Rd. 

 Middleton Industrial Park 

 Middleton, WI 53562

PH: (608) 831-2585 

 FAX (608) 831-7407

File Name: I0000138 Rev 6.Doc

Page 3 of 3

See 

Figure 7

 and 

Figure 8

 for two different current switch applications using your Building Management System (DDC/PLC

Controller).  

Figure 7

 is showing the use of the Adjustable Current Switch as a Digital Input to your DDC Controller, whereas

Figure 8

 is showing you how to use the Adjustable Current Switch in conjunction with your building management system to 

monitor belt loss on a motor.

(Status)

System

Digital Input #1

Building Management

24 VAC

120 VAC

Line

Transformer

(Relay Coil or

Contactor)

DO

DI

DDC Controller

24 VAC Coil

Relay / Contactor

                        Figure 7: Digital Circuit                                                                  Figure 8: Analog Circuit

 Calibration of Adjustable Trip Point

The adjustable current switch has an operating range of 0 to 200 or 0 to 250 Amps depending on the model being entered (see 

Figure #9).

  

Do not exceed!

  The adjustable current switch comes with its fifteen-turn adjustment potentiometer set counter

clockwise to the maximum 200 or 250A trip point position.  The adjustable current switch can monitor Under load, Normal Load, 
and Overload conditions, depending on how it’s set.  The procedure below is for the Normal load condition for part numbers 
A/ASCS & A/ASCS-L.

 Normal Loads

With power on, and the adjustable current switch on the proper range, turn the 15-turn adjustment potentiometer clockwise until the 
Red LED turns on and stop immediately.  The adjustable current switch is now tripped.  The adjustable current switch Hysteresis 
(Dead Band) is 10% of the trip point typically.

 Troubleshooting

Problem

Solution

Red LED is on but the current switch didn’t activate

Disconnect the wires from the current switch output.  Measure the 
resistance across the contacts with an Ohmmeter.  

See Figure 9

 for 

resistance readings for a good unit.

Red LED didn’t turn on and the current switch didn’t 
activate

Verify that the conductor you are monitoring is above the adjustable 
trip point.  If the sensor is monitoring less than the adjustable trip
point 

See Figure 5

 on Page 2.

Current Switch doesn't switch at all, regardless of current 
level. 

Adjustment potentiometer is probably set to its maximum or
minimum position.  Turn the Pot counter-clockwise all the way and 
verify if the LED switches from Red to Green.

ACI Model #

Resistance if switch open

Resistance if switch closed

A/ASCS

Greater than 1 Meg ohms

Approximately 2 ohms

A/ASCS-L

Greater than 1 Meg ohms

Approximately 2 ohms

A/ASCSX

Greater than 1 Meg ohms

Approximately 12 ohms

A/ASCSX-L

Greater than 1 Meg ohms

Approximately 12 ohms

Figure 9

 WEEE Directive

At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.  Do not dispose of 
with household waste.  Do not burn.
                                                                     

                                                                           

LISTED

C

US

IND.CONT.EQ.

3JHX

  

Reviews: