Operation

Diagnostic System

ACDC DCAC  Dane Krapcev no.2/1,  1000-Skopje, Macedonia    Phone: 389 2 3216 988;   Fax: 389 2 3216 993

Sur

Sur e

G

MULTI-STAGE SURGE PROTECTION

 www.acdc-dcac.eu

Every ACDC Surge Protector Type -PI (740; 780; 7125; 7200) Red Series have free contact alarm as basic option.  The alarm is activate in two cases:   

1. When some of the protection stages (2, 4 or 6) are damaged or burned and Red Led is ON.  Alarm contacts 1-3 are 

                               

permanently closed.  

2.  When the ground of the power grid system is not well performed (pour grounding). Alarm contacts1-3 are closing with frequency of 2Hz (0,5s)
Red led is blinking.                                 

Free contacts are on the cover of the protector with contact no. 1 and 3. (see picture)                                     
The contact is a optocoupler with maximum value of voltage 70VDC and current of 10mA. In normal condition it is open.

 .

  .    

1

3

N.C

+

-

Free Contact Alarm

Series

ACDC SURGE PROTECTOR

Red

MULTI-STAGE

SURGE

PROTECTION

CLASS I

II

III

++

1, 3, 7 and 8 Stage: Filter (bi-directional wave tracking); 

1, 3, 7 and 8 Stage: Filter (bi-directional wave tracking); 
3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz

3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz
2, 4 and 5 Stage:  Surge Limiter (L-N) 

2, 4 and 5 Stage:  Surge Limiter (L-N) 
150kA (8x20

150kA (8x20 s); 22kA (10/350

s); 22kA (10/350 s)

s)

6. Stage: MOSFET Limiter-500A (8x20

6. Stage: MOSFET Limiter-500A (8x20 s)(RT<1ns) 

s)(RT<1ns) 

9. Stage: Surge Limiter (N-Gnd)

9. Stage: Surge Limiter (N-Gnd)
125kA (8x20

125kA (8x20 s); 20kA (10/350

s); 20kA (10/350 s)

s)

                

                
              

              

μ

μ

μ

μ

μ

N

P

S

INE ROTECTION TAGES

 

 

Load Rating: 230VAC @ 100A 

Type - PI   Red   Series

L

N

IN

L

N

IN

IN

IN

PARALLEL

N

OUT

PARALLEL

N

OUT

L

L

PARALLEL

G

PARALLEL

G

L

L

IN

IN

ND

G

FAULT

L

G

L

G

II  
              

CORRECT

OUT

OUT

OUT

OUT

      IV,VI

CORRECT

Series

ACDC SURGE PROTECTOR

Red

MULTI-STAGE

SURGE

PROTECTION

CLASS I

II

III

++

N

IN

N

IN

1, 3, 7 and 8 Stage: Filter (bi-directional wave tracking); 

1, 3, 7 and 8 Stage: Filter (bi-directional wave tracking); 
3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz

3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz
2, 4 and 5 Stage:  Surge Limiter (L-N) 

2, 4 and 5 Stage:  Surge Limiter (L-N) 
150kA (8x20

150kA (8x20 s); 22kA (10/350

s); 22kA (10/350 s)

s)

6. Stage: MOSFET Limiter-500A (8x20

6. Stage: MOSFET Limiter-500A (8x20 s)(RT<1ns) 

s)(RT<1ns) 

9. Stage: Surge Limiter (N-Gnd)

9. Stage: Surge Limiter (N-Gnd)
125kA (8x20

125kA (8x20 s); 20kA (10/350

s); 20kA (10/350 s)

s)

                

                
              

              

μ

μ

μ

μ

μ

N

P

S

INE ROTECTION TAGES

 

 

Load Rating: 230VAC @ 100A 

Type - PI   Red   Series

L

L

IN

IN

N

OUT

N

OUT

PARALLEL

PARALLEL

L

L

PARALLEL

PARALLEL

G

G

L

L

IN

IN

G

ND

FAULT

G

G

L

L

II  
              

CORRECT

OUT

OUT

      IV,VI

OUT

OUT

CORRECT

Series

ACDC SURGE PROTECTOR

Red

MULTI-STAGE

SURGE

PROTECTION

CLASS I

II

III

++

1, 3, 7 and 8 Stage: Filter (bi-directional wave tracking); 

1, 3, 7 and 8 Stage: Filter (bi-directional wave tracking); 
3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz

3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz
2, 4 and 5 Stage:  Surge Limiter (L-N) 

2, 4 and 5 Stage:  Surge Limiter (L-N) 
150kA (8x20

150kA (8x20 s); 22kA (10/350

s); 22kA (10/350 s)

s)

6. Stage: MOSFET Limiter-500A (8x20

6. Stage: MOSFET Limiter-500A (8x20 s)(RT<1ns) 

s)(RT<1ns) 

9. Stage: Surge Limiter (N-Gnd)

9. Stage: Surge Limiter (N-Gnd)
125kA (8x20

125kA (8x20 s); 20kA (10/350

s); 20kA (10/350 s)

s)

                

                
              

              

μ

μ

μ

μ

μ

N

P

S

INE ROTECTION TAGES

 

 

Load Rating: 230VAC @ 100A 

Type - PI   Red   Series

L

N

IN

L

N

IN

IN

IN

PARALLEL

N

OUT

PARALLEL

N

OUT

L

L

PARALLEL

G

PARALLEL

G

L

L

IN

IN

ND

G

FAULT

L

G

L

G

II  
              

CORRECT

OUT

OUT

OUT

OUT

      IV,VI

CORRECT

mark 
                
              

1 3

+

-

mark 
                
              

mark 
                
              

Led Indication for correct stage no. 2,4 and 6. The 

 .

stages

 no. 1,3,7 and 8 (high 

garde bi-directional filtering) are always in function along with ultimate (5-th) 
protection stage

Led Indication for correct stage no. 4,6 and un correct no 2.  The 

 .

stages

 no. 1,3,7 

and 8 (bi-directional filtering) are always in function along with ultimate (5-th) 
protection stage

Only stages 1,3,7 and 8 are still in function along with ultimate (5-th) protection 
stage.

Led Indication for bed grounding (Low impedance equipotential  ground is not 
provided)

Normal:

Fault:

Fault:

Fault:

Red

Yellow

Green

Continuous yellow
and green

Continuous green

Blinking red

Continuous red

Connection  for  ommon   ontact  larm

 c

  c

 a

Operation   Diagnostic   System