Mounting of ACDC Surge Protectors

ACDC Surge Protectors

Series have to be installed at ENTRY POINT 

the Main 

Distribution Boards (MDB) or

internal Sub Distribution Boards (SDB)  right in front of the input power to the device that should be protected The ACDC Surge Protector
could be install in series or parallel configuration depending of total load per phase (>100A<). 

- If the load per phase is <100A the ACDC Surge Protector 

 install  in SERIES configuration. 

- If the load per phase is >100A the ACDC Surge Protector must be installed in PARALLEL configuration.   

 Type-PI 3/3 - M  Red 

before 

Power 

 

 or

have to be

ed

                                    Only in SERIES configuration all nine (9) protection stages are in function.

            

ACDC Surge Protectors are designed to fixed to the wall 

.             

2

2

 

             

1.  

 

                    

                          

             

If the the load per phase is <100A, our RECOMMENDATION is to install the surge protector in SERIES configuration 

because only in this state your electrical devices will be fully protected. 

If the total load per phase is >100A and ACDC Surge Protector is installed in PARALLEL configuration our 

RECOMMENDATION is to install another ACDC Surge Protector in SERIES configuration ( 

Sub Distribution Board), 

downstream power grid where the load per phase drops bellow 100A, 

   

            

 before 

Condition for Installations: 

Mounting:                          

Terminal and Wire size:

                                    

During the installation please check:

                                    

                                 

with screws

Each terminal is designed to accept wire sizes from 4mm  to 25mm  solid or stranded conductor. The wire insulation should be stripped back 
8mm

The voltage of the ACDC Surge Protector matches actual system voltage.                                 

2. All conductors are in accordance with the appropriate installation drawings.

THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL.

Before installing the ACDC Surge Protector, AC power must be OFF. 

CORRECT INSTALLATION - THE LIGHTS GREEN AND YELLOW ARE LIT 

TROUBLESHOOTING - IF THE RED LED IS BLINKING THE GROUND WIRE IS NOT CONNECTED OR THE GROUND OF THE 

POWER GRID SYSTEM IN NOT WELL PERFORMED

-  rovides adequate electrical and safety protection
- Prevents the ingress of moisture and water
- Allows operating diagnostic status to be inspected