Accutrol ZPS-H Quick Start Manual Download Page 3

www.accutrolllc.com

 

 

 

 

3

 

 

ZPS-H QUICK START GUIDE Rev. L    11/4/2020

 

 

 

 

STEP 2: START UP 
2a. Power up 

Apply Power to unit and wait for LEDs to illuminate.  
  

 

 

 

 

 
LED lights solid (Green = no detection,  Red = detection)  

  
2b. Adjustment of Switch Positions 

Verify all switch positions are set to factory default as shown to the right.

 

Note: Factory Default Switch Positions are Highlighted grey. 

 

2c. Adjustment with Cover Off

 

To quickly adjust pattern, press and release the Reset Button and then press and hold the Install Button for 3 seconds 
(the LED will flash orange to confirm).  This puts the ZPS-H into an install mode that is constantly sensing, but not 
driving the signal to the AVC.  Test unit by walking in and out of the area in front of the hood, watch the LED and it will 
turn red when it senses a person. 

 

 

The sensor should be activated regardless if the person walks towards or away from it.   If the unit does not sense 
presence appropriately, tip the sensor head in or out until it does.  Walk in and out of the area several times to test.  

 

  

 
 

  

 

2d. Sensitivity Adjustment 

If you need to increase the sensitivity of the ZPS-H, adjust the knob marked “range” clockwise. When you are satisfied 
with the sensitivity of the unit, depress the Reset Button

 

again and the ZPS-H will go into Normal Operating mode.

 

 

SW 

SWITCH POSITION 

DESCRIPTIONS 

LEFT 

RIGHT 

NOT USED 

NOT USED 

FAILSAFE 
OFF 

FAILSAFE 
ON 

HPR OFF 

HPR ON 

NOT USED 

NOT USED 

DEPART 

APPROACH 

BI-
DIRECTION 

UNI-
DIRECTION 

Install Button

 

Reset Button

 

Range Sensitivity

 