ZPS-H QUICK START GUIDE Rev. L    11/4/2020

 

 

 

 

 
 

Note:  Please  read  this  entire  document  to  familiarize  yourself  with  the  installation  and  wiring 

instructions  for  the  ZPS-H  Hood  Presence  Sensor.  For  additional  details,  refer  to  the  individual  product 
Submittal Drawings, User Manuals and Job-Specific Requirements.  

OVERVIEW 

The ZPS-H Zone Presence Sensor is an optional sensor used with the AVC Fume Hood Control System, which will 
cause the Fume Hood Monitor to revert to the Setback mode when no one is standing in front of the hood thus reducing 
the exhaust requirements. Upon the return of the occupant to the front of the hood, the ZPS-H will immediately signal 
the AVC Fume Hood Control System to return to the normal working velocity set point. 

STEP 1: INSTALLATION 

Caution: Wear eye protection, cut resistant gloves and clothing suitable for working with sheet metal.  

Failure to do so may result in personal injury. 
1a. Location 

Select a flat surface on the front of the fume hood above the operator. Verify there is enough clearance behind the 
panel to accommodate the two mounting screws and the cable. If the location is suitable, adhere the mounting template 
to the surface. 

  

 

 

 

 

 

1b.  Prepare the Area 

Using the mounting template as a guide, drill two holes for the mounting screws and one hole for the cable.  

Caution: Be sure to deburr the cable hole prior to inserting cable through the hole to prevent cable 

damage. 

Insert the provided cable through the hole from the front of the hood so that the terminal block is on the front of the 
panel. Insert mounting screws provided with kit partially, leaving space under the screw heads to slip the sensors slotted 
holes under. 

  

 

 

 

     Power Cable and partially installed Screw              Insert Screwdriver and Pry Upwards to Remove Cover 

 

 

 

 

Quick Start Guide

 

 

ZPS-H (Zone Presence Sensor for Fume Hood Applications) 

 

 

                            

 

Sash

To AVC

Exhaust Duct

Front  Hood Panel

ZPS-H (On  top of  

Hood)

 Pictured is the top-down view of the hood 
showing ZPS-H cable routing.  Be sure the 
sash and any of its moving parts do not 
interfere with the Zone Presence Sensor 
Cable.

 

 