Installation & Operation Manual - Model AVC6000
Contents of this Manual are Subject to Change Without Notification
Page 17
Note:
If 24VAC is applied then the USB is connected beforehand, or if
the switch position is changed while a USB connection is active, the
controller will revert to bootloader mode and will not function properly.
Note:
If a controller is in bootloader mode, disconnect the USB,
disconnect the 24VAC power, ensure the power source switch is set to
the “operational position”, and wait 5 seconds. After these steps,
reconnecting 24VAC power first will resume normal operation.
6.4
Connecting the PC to the AVC Control Module
6.4.1
Connecting to a standard AVC6000 using USB cable
6.4.1.1
Power Source Switch
The AVC6000 controller has a Power Source Switch which should always be in the
“Operational Position” for the
controller
to function normally. The “Nonoperational
Position” is provided so the
controller can be programmed or configured when there is no
24v power source available. This is a convenient feature for configuring the BACnet
parameters or the controller
’s analog o
utput prior to having the 24v power source wired.
Operational Position
Nonoperational Position
24v power is provided to the controller
through the 24v connector. This is the
normal position for the Power Source
Switch.
5vdc power is provided to the controller
through the computer connected to the
USB Configuration Port. This is a
temporary position only.
Note:
The Power Source Switch must be returned to the Operational Position after
completing the configuration otherwise the controller will not function.
AVC6000
Windows 10 Device with
AccuValve Insight Software
USB Cable
with C-type
Connector