6
Ductwork
Electrical Connections
Access for wiring the hood control panel (when applicable) is provided by a junction box located on
top of the hood when the control panel is mounted in the hood, or by the switch junction box when the
control panel is mounted in the fire protection cabinet. The box is labeled “Control Voltage Wiring to
Roof Top Fan Package”. Use minimum 14 AWG copper wire.
Standard light switches for remote mounting are rated for 15 amps and shall not have more than 14
lights connected to them. Higher amperage switches are available upon special request.
Exhaust
As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust duct systems must be constructed in the
following manner:
Materials
. Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm
(0.054 in.) (No. 16 MSG) in thickness or stainless steel not less than 1.09 mm (0.043 in.) (No. 18 MSG) in
thickness.
Installation.
All seams, joints, penetrations, and duct-to-hood collar connections shall have a
liquid-tight continuous external weld.
Supply
Supply ductwork (where applicable) should be connected to the hood in a manner approved by the
local code authorities.
Note: For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning
and inspection shall be provided in the duct. This panel shall be as close to the hood as possible but
should not exceed 18 in. (45.7 cm).
For proper installation of duct collars when they are shipped unattached, see page 14
External Supply
Plenum Type
Weight
Width
Height
Length per
section
Recommended
Supply Rate
(lbs/ft)
(kg/ft)
(in)
(mm)
(in)
(mm)
(ft)
(m)
Back Supply
35.0
15.878
6
15.4
Variable
Variable
3 to 16
.91 to
4.88
145 cfm/ft
(46.36 m
3
/hr)
Air CurtainSupply
• 14 inch
9.5
4.31
14
355.6
10
54
3 to 16
.91 to
4.88
110 cfm/ft
(186.89 m
3
/hr)
Air Curtain Supply
• 4 inch
1.5
5.67
4
609.6
10
54
3 to 16
.91 to
4.88
145 cfm/ft
(46.36 m
3
/hr)
Variable Supply
16.0
7.6
1
304.8
18
457.0
3 to 16
.91 to
4.88
face
80-160 cfm/ft
(135.9 -71.84 m
3
/hr)
Horizontal Supply
14.0
6.35
1
304.8
18
457.0
3 to 16
.91 to
4.88
150 cfm/ft
(54.85 m
3
/hr)
External Supply Plenum Weights, Dimensions, and Supply Rates