AXM-MESH MODULE
ATTACHING TO A METER - ACUVIM II CONFIGURATION:
With the AXM-Mesh module attached to the meter, the meter should be
configured with the following settings to communicate:
Protocol 2:
Mesh
NOTE:
By changing the ‘Protocol 2’ setting to Mesh in the meter this will
automatically change the Baud rate 2 setting in the meter to 9600 and Parity 2
to None1
If the meter does not have Mesh option in Protocol 2, please set Baud rate 2 and
Parity 2 to 9600 and None1 respectively.
CONFIGURATION WITH OTHER DEVICES:
For other meters or devices that communicate through a RS485 port, the devices
must have the following settings to communicate with the transceiver:
Baud rate:
9600
Parity:
None1 (Or Parity None, stop bit 1)
NOTES:
The Acuvim II meters and any other RS485 connected devices in the network
should be assigned with a unique Modbus address from 1-247.
The standalone transceiver can only be connected either via USB or via RS485 at
any time.