18
ENGLISH
Commissioning
Reg # Register Name
Default Range of Adjustment Important
32
Total kWh (low word)
Read only. See P511 in drive manual
33
Total kWh (high word)
37
Actual PID setpoint
0.0
-999.0 … 3100.0
Read only. See section 9.2.8
38
PID Setpoint Command
0.0
-999.0 … 3100.0
Read only. See section 9.2.8
39
PID Feedback
0.0
-999.0 … 3100.0
Read only. See section 9.2.8
40
Keypad Speed Command
20.0 Hz
P102 … P103
41
Keypad PID Setpoint Command
0.0
-999.0 … 3100.0
Read only. See section 9.2.8
42
Keypad Torque Command
100%
0.0 … 400.0
44
Network Speed Command
0.0 Hz
P102 … P103
See Section 8.3
45
Network PID Setpoint Command
0.0
-999.0 … 3100.0
Read-only See Sections 8.3 and 9.2.8
46
Network Torque Command
0%
0.0 … 400.0
See Sections 8.3
48
Unlock Controls
See Sections 7.3
49
Unlock Parameters
See Sections 7.3
50
Parameter Version
Read only. See section 9.2.9
60
Total Run Time hours (low word)
Read only. See P540 in drive manual
61
Total Run Time hours (high word)
64
Total Power-on Hours (low word)
Read only. See P541 in drive manual
65
Total Power-on Hours (high word)
70
Network Controlled Digital Output
(TB14) + Relay
0: de-energized, 1: energized
bit 9: TB-14 state
bit 10: Relay state
other bits are not used
See section 9.2.10
71
Network Controlled Analog Output
0.0%
0.0 … 100.0
See section 9.2.11