•  Units require horizontal roof curb and return air kit for 

horizontal installations.

•  Ductwork  should  be  attached  directly  to  flanges  on 

panels supplied in horizontal duct conversion kits.

Rooftop

Rooftop installations must be located according to local 

building codes or ordinances and these requirements:

•  The roof must be capable of handling the weight of the 

unit. For unit weights, see 

Table 4 (page 13)

. Reinforce 

the roof if necessary.

•  The appropriate accessory roof curb (

Figure 4

) must be 

installed prior to unit installation. The roof curb must be 

square and level to ensure proper condensate drainage. 

Please follow all instructions provided with the kit

.

•  Secure  roof  curb  or  frame  to  roof  using  acceptable

 

mechanical methods per local codes. 

notE:

 

Make sure 

the two supports beneath the unit have been removed. 

Roof

Curb

Figure 4. Roof top Installation

Figure 5. condensate Drain location

ElEctRIcAl WIRInG

 WARnInG:

to avoid risk of electrical shock, personal injury, 

or death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical supply.
label all wires prior to disconnection when 

servicing the unit. Wiring errors can cause 

improper and dangerous operation

•  Electrical  connections  must  be  in  compliance  with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For  Canadian  installations  the  electrical  connections 

and grounding shall comply with the current Canadian 

Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical checklist:

 Verify that the voltage, frequency, and phase of the 

supply source match the specifications on the unit rating 

plate.

  Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

refer to the unit wiring label for proper high and low 

voltage wiring.

  Verify factory wiring is in accordance with the unit wiring 

diagram. See 

Figure 8 (page 15)

. Inspect for loose 

connections.

line Voltage

•  A wiring diagram is located on the inside cover of the 

units electrical box. The installer should become familiar 

with the wiring diagram before making any electrical 
connections to the outdoor unit.

• 

An electrical disconnect must be located within sight 

of and readily accessible to the unit. 

This switch shall 

be capable of electrically de-energizing the unit.

•  Line  voltage  to  the  unit  should  be  supplied  from  a 

dedicated branch circuit containing the correct fuse 

or circuit breaker for the unit. Incoming field wiring 

Condensate

Drain

Horizontal to Downflow conversion

The unit is shipped ready for horizontal duct connections. 

If down flow ducts are required, the unit must be converted 

following the steps below for the supply and return ducts.

1. Locate the duct cap inside the duct openings and remove 

the screw holding it in place.

2. Lift the cap out of the unit. (

Hint: 

The cap can be pushed 

up from the bottom by reaching through the fork slot).

3. Cover the horizontal duct opening with the horizontal 

duct cap. The insulation will be on the indoor side.

4. Fasten the cover with screws to seal.

condensate Drain

Condensate is removed from the unit through the 3/4” 

female pipe fitting located on the front side of the unit. 

Install a 2 inch condensate trap in the drain line of the 

same size and prime with water. See 

Figure 5

.

When connecting rigid drain line, hold the female fitting 

with a wrench to prevent twisting. 

Do not over tighten!

 

Refer to local codes and restrictions for proper condensate 

disposal requirements.

Summary of Contents for Q6SE Series

Page 1: ...common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local code...

Page 2: ... an R 410A Unit in AC Mode 12 Charging an R 410A Unit in Heating Mode 12 REPLACEMENT PARTS 12 FIGURES TABLES 13 Figure 6 Q6SE Heat pump Dimensions 13 Table 4 Center of Gravity Unit Shipping Weights 13 Electrical Information 14 Figure 7 Typical Heat Pump Thermostat Connections 208V 230V 14 Figure 8 Wiring Diagram for 208 230V Units 15 Cooling Charging Charts 16 Figure 9 Charging Chart for 2 Ton Uni...

Page 3: ...tthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the fan and compressor in the outdoor unit may not start immediately A protective timer circuit holds the compressor and the outdoor fan off for ...

Page 4: ... system will not operate regardless of the temperature selector setting HEAT PUMP MAINTENANCE CAUTION Shut off all electrical power to the unit before performing any maintenance or service on the system Failure to comply may result in personal injury or death Proper maintenance is most important to achieve the best performancefromtheapplianceandshouldbeperformed by a qualified service technician a...

Page 5: ...soline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit Unqualified individuals shouldnotattempttointerprettheseinstructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious personal ...

Page 6: ...it The cooling load of the area to be conditioned must be calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the electrical supply and verify the power supply is adequate for unit operation If there is any question concerning the power supply contact the local power company Allunitsaresecurelypackedatthet...

Page 7: ...nit weights The unit must be lifted from the holes in the base rails using cables or chains Spreader bars are required to protect the unit and ensure even loading Keep the unit in an upright position at all times The rigging must be located outside the units center of gravity Refer to Figure 6 page 13 for locating the center of gravity All panels must be securely in place during rigging and hoisti...

Page 8: ...ecificationsontheunitrating plate Verify that the service provided by the utility is sufficient tohandletheadditionalloadimposedbythisequipment refer to the unit wiring label for proper high and low voltage wiring Verify factory wiring is in accordance with the unit wiring diagram See Figure 8 page 15 Inspect for loose connections Line Voltage A wiring diagram is located on the inside cover of the...

Page 9: ...inimizepersonal injury if an electrical fault should occur Do not use gas piping as an electrical ground This unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit Blower Speed The blower speed is prese...

Page 10: ...ture is available by selecting a different demand curve NOTE The 30 secondcompressordelayfunctionisoptionalandbased on the demand curve selected Thestandarddefrostcyclewillterminateafter13minutes and 39 seconds or when the coil temperature reaches its terminate temperature whichever occurs first Thedefrostboardisequippedwitha5minuteAnti Short Cycle Delay ASCD The compressor will not turn on until ...

Page 11: ...Figure 14 page 18 START UP adjustments Pre Start Check List Verify the unit is level and allows condensate to drain Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment access control panels are in place Verifythattheductworkissealedtopreventairleakage Verify that the line voltage power leads are securely connected and the unit is properly grounded Ve...

Page 12: ...sors Transformers Contactors Motors Blower Motor Fan Motor Components Blower Assembly Fan Grille Cabinet Panels Filter Driers Expansion Valves HEAT PUMP MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service Unit may have more than one electrical supply CAUTION Use care when servicing the hea...

Page 13: ... 39 3 X60 580 29 5 26 0 43 0 39 3 FIGURES TABLES Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAL SUPPLY DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Side View 1 1 4 Ø Power Entry 1 3 4 Ø Power Entry Ca...

Page 14: ...UG Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat E E R W2 R W2 O Y C O Y C T2 T1 DFT Optional Outdoor Thermostat Field Supplied Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat E R W2 O Y1 C Y2 G E R W2 O Y C E R W2 DFT 1 2 3 4 5 6 7 8 9 Brown Orange ECONOMIZER PLUG INDOOR THERMOSTAT SUB BASE SEE ECONOMIZER INSTALLATION...

Page 15: ... temperature rating of at least 105 C 5 For supply wire ampacities overcurrent protection see unit rating plate 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre 10064970 11 14 NOTE See Installation Instructions for wiring application and Information concerning accessory Heat Kits and other o...

Page 16: ...nt if above curve Add refrigerant if below curve Figure 9 Charging Chart for 2 Ton Units 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig Q6SE X30 CHARGING CHART COOLING 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve Figure 10 Charging Chart for 2 5 Ton Unit...

Page 17: ... 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve Figure 12 Charging Chart for 3 5 Ton Units 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig Q6SE X36 CHARGING CHART COOLING 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant ...

Page 18: ...ove refrigerant if above curve Add refrigerant if below curve Figure 13 Charging Chart for 4 Ton Units 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig Q6SE X60 CHARGING CHART COOLING 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve Figure 14 Charging Chart fo...

Page 19: ...58 19 06 1596 19 80 1534 20 60 1481 21 33 1421 22 23 1358 23 27 1279 24 70 X42 Tap T1 1257 25 13 1199 26 35 1133 27 89 1070 29 53 982 32 17 906 34 87 830 38 06 761 41 52 Tap T2 1374 22 99 1332 23 72 1270 24 88 1220 25 90 1153 27 40 1077 29 34 972 32 50 901 35 07 Tap T3 1574 20 07 1520 20 79 1470 21 49 1418 22 28 1356 23 30 1295 24 40 1214 26 02 1095 28 85 Tap T4 1733 18 23 1678 18 83 1637 19 30 15...

Page 20: ..._______________ INSTALLER PLEASE LEAVE THESE INSTRUCTIONS WITH THE OWNER INSTALLATION ADDRESS CITY_________________________ STATE_________________ UNIT MODEL _________________________________________ UNIT SERIAL _________________________________________ UnitInstalledMinimumclearancesper Figure 2 page 6 YES NO INSTALLER NAME CITY________________________ STATE_________________ Has the owner s inform...

Reviews: