AC Pro Q6SE Series User Manual Download Page 6

6

Warm Air Heating and Air Conditioning Systems (NFPA 

90B), and all applicable local codes. NFPA publications 

are avaialable by writing to: National Fire Protection 

Association, Batterymarch Park, Quincy, ME 02269 or 

visit www.NFPA.org on the web.

•  Design the duct work according to methods described 

by the Air Conditioning Contractors of America (ACCA). 

•  The ducts must be properly sized not to exceed .2” W.C. 

pressure drop at 400 scfm per nominal ton of cooling 

capacity.

•  Duct work should be attached directly to the unit flanges 

for horizontal applications.

•  If roof curb is installed, the ducts must be attached to 

the curb hangers, not the unit.

Unconditioned Spaces

All duct work passing through unconditioned space must 

be properly insulated to minimize duct losses and prevent 

condensation. Use insulation with an outer vapor barrier. 

Refer to local codes for insulation material requirements.

Acoustical Duct Work

Certain installations may require the use of acoustical 

lining inside the supply duct work.

•  Acoustical insulation must be in accordance with the 

current revision of the Sheet Metal and Air Conditioning 

Contractors National Association (SMACNA) application 

standard for duct liners.

•  Duct lining must be UL classified batts or blankets with 

a fire hazard classification of FHC-25/50 or less. 

•  Fiber duct work may be used in place of internal duct 

liners if the fiber duct work is in accordance with the 

current revision of the SMACNA construction standard 

on fibrous glass ducts. Fibrous duct work and internal 

acoustical lining must be NFPA Class 1 air ducts when 
tested per UL Standard 181 for Class 1 ducts.

GEnERAl InFoRMAtIon

The Q6SE series heat pump is designed only for outdoor 

rooftop or ground level installations. This unit has been 

tested for capacity and efficiency in accordance with 

AHRI Standards and will provide many years of safe 

and dependable comfort, providing it is properly installed 

and maintained. Abuse, improper use, and/or improper 

maintenance can shorten the life of the appliance and 

create unsafe hazards.

Before you install this unit

  The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. If there is any question 

concerning the power supply, contact the local power 

company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage (apparent or 

concealed) should be filed immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

locating the Heat Pump

•  Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Choose  an  appropriate  location  that  minimizes  the 

length of the supply and return air ducts.

•  Overhead  obstructions,  poorly  ventilated  areas,  and 

areas subject to accumulation of debris should be 

avoided.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. See 

Figure 2

 for minimum clearances to 

obstructions.

Field connections for Electrical Power Supply

•  All wiring must comply with current provisions of the 

National Electrical Code (ANSI/NFPA 70) and with 

applicable local codes having jurisdiction.

•  The minimum size of electrical conductors and circuit 

protection must be in compliance with information listed 

on the outdoor unit data label.

•  Electrical power supplied to the unit must be adequate 

for proper operation of the equipment. The system 

must be wired and provided with circuit protection in 
accordance with local building codes.

Air Ducts

This unit is designed only for use with a supply and return 

duct. Air ducts must be installed in accordance with the 

standards of the National Fire Protection Association 

Standard for Installation of Air Conditioning Systems 

(NFPA 90A), Standard for Installation of Residence Type 

Minimum Required 

Clearances to Obstructions

36"

36"

36"

36"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

Figure 2. clearance Requirements

Summary of Contents for Q6SE Series

Page 1: ...common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local code...

Page 2: ... an R 410A Unit in AC Mode 12 Charging an R 410A Unit in Heating Mode 12 REPLACEMENT PARTS 12 FIGURES TABLES 13 Figure 6 Q6SE Heat pump Dimensions 13 Table 4 Center of Gravity Unit Shipping Weights 13 Electrical Information 14 Figure 7 Typical Heat Pump Thermostat Connections 208V 230V 14 Figure 8 Wiring Diagram for 208 230V Units 15 Cooling Charging Charts 16 Figure 9 Charging Chart for 2 Ton Uni...

Page 3: ...tthetemperatureselectortothedesiredtemperature level Theoutdoorfan compressor andblowermotorwill all cycle on and off to maintain the indoor temperature at the desired cooling level NOTE If the temperature level is re adjusted or the system mode is reset the fan and compressor in the outdoor unit may not start immediately A protective timer circuit holds the compressor and the outdoor fan off for ...

Page 4: ... system will not operate regardless of the temperature selector setting HEAT PUMP MAINTENANCE CAUTION Shut off all electrical power to the unit before performing any maintenance or service on the system Failure to comply may result in personal injury or death Proper maintenance is most important to achieve the best performancefromtheapplianceandshouldbeperformed by a qualified service technician a...

Page 5: ...soline and any other flammable vapors and liquids in the vicinity of the unit WARNING The safety information listed below must be followed during the installation service and operation of this unit Unqualified individuals shouldnotattempttointerprettheseinstructions or install this equipment Failure to follow safety recommendations could result in possible damage to the equipment serious personal ...

Page 6: ...it The cooling load of the area to be conditioned must be calculatedandasystemofthepropercapacityselected It is recommended that the area to be conditioned be completely insulated and vapor sealed Check the electrical supply and verify the power supply is adequate for unit operation If there is any question concerning the power supply contact the local power company Allunitsaresecurelypackedatthet...

Page 7: ...nit weights The unit must be lifted from the holes in the base rails using cables or chains Spreader bars are required to protect the unit and ensure even loading Keep the unit in an upright position at all times The rigging must be located outside the units center of gravity Refer to Figure 6 page 13 for locating the center of gravity All panels must be securely in place during rigging and hoisti...

Page 8: ...ecificationsontheunitrating plate Verify that the service provided by the utility is sufficient tohandletheadditionalloadimposedbythisequipment refer to the unit wiring label for proper high and low voltage wiring Verify factory wiring is in accordance with the unit wiring diagram See Figure 8 page 15 Inspect for loose connections Line Voltage A wiring diagram is located on the inside cover of the...

Page 9: ...inimizepersonal injury if an electrical fault should occur Do not use gas piping as an electrical ground This unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit Blower Speed The blower speed is prese...

Page 10: ...ture is available by selecting a different demand curve NOTE The 30 secondcompressordelayfunctionisoptionalandbased on the demand curve selected Thestandarddefrostcyclewillterminateafter13minutes and 39 seconds or when the coil temperature reaches its terminate temperature whichever occurs first Thedefrostboardisequippedwitha5minuteAnti Short Cycle Delay ASCD The compressor will not turn on until ...

Page 11: ...Figure 14 page 18 START UP adjustments Pre Start Check List Verify the unit is level and allows condensate to drain Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment access control panels are in place Verifythattheductworkissealedtopreventairleakage Verify that the line voltage power leads are securely connected and the unit is properly grounded Ve...

Page 12: ...sors Transformers Contactors Motors Blower Motor Fan Motor Components Blower Assembly Fan Grille Cabinet Panels Filter Driers Expansion Valves HEAT PUMP MAINTENANCE WARNING To prevent electrical shock personal injury or death disconnect all electrical power to the unit before performing any maintenance or service Unit may have more than one electrical supply CAUTION Use care when servicing the hea...

Page 13: ... 39 3 X60 580 29 5 26 0 43 0 39 3 FIGURES TABLES Top View 24 9 13 5 16 12 13 3 13 5 16 12 CG A 47 5 75 NPT Female Drain Connector B DOWNFLOW SUPPLY DUCT OPENING DOWNFLOW RETURN DUCT OPENING 23 5 Back View 13 5 16 0 13 7 13 5 16 0 12 45 11 75 22 75 55 8 C HORIZONTAL SUPPLY DUCT OPENING HORIZONTAL RETURN DUCT OPENING 4 0 CONDENSING COIL 5 0 8 4 00 Side View 1 1 4 Ø Power Entry 1 3 4 Ø Power Entry Ca...

Page 14: ...UG Typical Wiring Field Supplied for 1 Stage Cool 1 Stage Electric Heat E E R W2 R W2 O Y C O Y C T2 T1 DFT Optional Outdoor Thermostat Field Supplied Typical Wiring Field Supplied for 2 Stage Cool 2 Stage Electric Heat with an Optional Outdoor Thermostat E R W2 O Y1 C Y2 G E R W2 O Y C E R W2 DFT 1 2 3 4 5 6 7 8 9 Brown Orange ECONOMIZER PLUG INDOOR THERMOSTAT SUB BASE SEE ECONOMIZER INSTALLATION...

Page 15: ... temperature rating of at least 105 C 5 For supply wire ampacities overcurrent protection see unit rating plate 1 Couper le courant avant de faire letretien 2 Employez uniquement des conducteurs en cuivre 3 Ne convient pas aux installations de plus de 150 V a la terre 10064970 11 14 NOTE See Installation Instructions for wiring application and Information concerning accessory Heat Kits and other o...

Page 16: ...nt if above curve Add refrigerant if below curve Figure 9 Charging Chart for 2 Ton Units 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig Q6SE X30 CHARGING CHART COOLING 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve Figure 10 Charging Chart for 2 5 Ton Unit...

Page 17: ... 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve Figure 12 Charging Chart for 3 5 Ton Units 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig Q6SE X36 CHARGING CHART COOLING 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant ...

Page 18: ...ove refrigerant if above curve Add refrigerant if below curve Figure 13 Charging Chart for 4 Ton Units 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig Q6SE X60 CHARGING CHART COOLING 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve Figure 14 Charging Chart fo...

Page 19: ...58 19 06 1596 19 80 1534 20 60 1481 21 33 1421 22 23 1358 23 27 1279 24 70 X42 Tap T1 1257 25 13 1199 26 35 1133 27 89 1070 29 53 982 32 17 906 34 87 830 38 06 761 41 52 Tap T2 1374 22 99 1332 23 72 1270 24 88 1220 25 90 1153 27 40 1077 29 34 972 32 50 901 35 07 Tap T3 1574 20 07 1520 20 79 1470 21 49 1418 22 28 1356 23 30 1295 24 40 1214 26 02 1095 28 85 Tap T4 1733 18 23 1678 18 83 1637 19 30 15...

Page 20: ..._______________ INSTALLER PLEASE LEAVE THESE INSTRUCTIONS WITH THE OWNER INSTALLATION ADDRESS CITY_________________________ STATE_________________ UNIT MODEL _________________________________________ UNIT SERIAL _________________________________________ UnitInstalledMinimumclearancesper Figure 2 page 6 YES NO INSTALLER NAME CITY________________________ STATE_________________ Has the owner s inform...

Reviews: