20
PROGRAMMING
AUTO MODE (LOW HUMIDITY TRIGGER)
Pressing the up or down button sets the low humid-
ity trigger. The devices will activate if the probe’s
reading meets or falls below this threshold.
Once triggered, the devices will gradually ramp up
to the level set in ON mode. If the probe’s reading
rises above this trigger point, the devices will
gradually slow down to a stop or at the level set in
OFF Mode.
You may set this trigger above the high humidity
trigger to create a range in which the devices are
active.
Note that this trigger can activate as long
as you are in AUTO Mode, even if you are
viewing a different trigger within AUTO Mode.
If there is a level set in OFF Mode other than
zero, the devices will run at that level when
triggered to turn off.
AUTO MODE (HIGH HUMIDITY TRIGGER)
Pressing the up or down button sets the high
humidity trigger. The devices will activate if the
probe’s reading meets or exceeds this threshold.
Once triggered, the devices will gradually ramp up
to the level set in ON mode. If the probe’s reading
falls below this trigger point, the devices will
gradually slow down to a stop or at the level set in
OFF mode.
You may set this trigger below the low humidity
trigger to create a specific range in which the
devices are active.
Note that this trigger can activate as long
as you are in AUTO Mode, even if you are
viewing a different trigger within AUTO Mode.
If there is a level set in OFF Mode other than
zero, the devices will run at that level when
triggered to turn off.