Installation/Removal, Calibration, Output Test, Operation 

APD 6380

Spring Clip

Upper Mount

Lower Mount

Mounting to a DIN Rail

Install module vertically on a 35 mm DIN rail in a protective 
enclosure away from heat sources. Do not block air flow. Allow 
1" (25 mm) above and below housing vents for air circulation.

1

2

Removal

Avoid shock hazards! Turn signal input, output, and power off 
before removing module.
1.  Push up on bottom back of module.
2.  Tilt front of module downward to release Upper Mount from top  

edge of DIN rail. 

3.  The module can now be removed  

from the DIN rail.

Calibration

Input and output ranges, if specified on your order, are factory 
pre-configured (at 24°C ±1°C). 
Front-mounted Zero and Span potentiometers are used to 
calibrate the output to compensate for load and lead variations.
Note: Perform the following calibration procedure any time 
switch settings are changed.
1.  Apply power to the module and allow a minimum 20 min-

ute warm up time.

2.  Using an accurate calibration source, provide an input to 

the module equal to the minimum input required for the 
application.

3.  Using an accurate measurement device for the output, 

adjust the Zero potentiometer for the exact minimum 
output desired. The Zero control should only be adjusted 
when the input signal is at its minimum. This will produce 
the corresponding minimum output signal.  For example: 4 
mA for a 4-20 mA output or –10 V for a ±10V output.

4.  Set the input at maximum and adjust the Span pot for the 

exact maximum output desired. The Span control should 
only be adjusted when the input signal is at its maximum. 
This will produce the corresponding maximum output 
signal. Example: for 4-20 mA output, the Span control will 
provide adjustment for the 20 mA or high end of the signal.

5.  Repeat adjustments for maximum accuracy.

Output Test Function

When the Test button is depressed it will drive the output with a 
known good signal that can be used as a diagnostic aid during 
initial start-up or troubleshooting. When released, the output 
will return to normal.
The Test Cal. potentiometer is factory set to approximately 
50% output. It can be adjusted to set the test output from 0 to 
100% of the output span. Press and hold the Test button and 
adjust the Test Cal. potentiometer for the desired output level.

Operation

The APD 6380 accepts an AC voltage or current input and 
provides an optically isolated DC voltage or current output that 
is linearly related to the input. 
The green LoopTracker

®

 input LED provides a visual indication 

that a signal is being sensed by the input circuitry of the mod-
ule. It also indicates the input signal strength by changing in 
intensity as the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as 
the process changes, check the module power or signal input 
wiring. Note that it may be difficult to see the LEDs under bright 
lighting conditions.
The red LoopTracker output LED provides a visual indication 
that the output signal is functioning. It becomes brighter as 
the input and the corresponding output change from minimum 
to maximum. 
For current outputs, the red LED will only light if the output loop 
current path is complete. For either current or voltage outputs, 
failure to illuminate or a failure to change in intensity as the 
process changes may indicate a problem with the module 
power or signal output wiring. 

Test Cal.

Span

Zero

Test

Output

Input

Loop
Tracker

APD 6380

AC to DC

Isolated Transmitter

Loop
Tracker

3. Push front of module 

upward until Upper Mount 
snaps into place. 

1.  Tilt front of module down-

ward and position against 
DIN rail. 

2.  Clip Lower Mount to bot-

tom edge of DIN rail. 

Installation

1

2

3

Output Test Level 

Adjustment

Push to Test 

Output

Output Span 

Calibration

Output Zero 

Calibration

Variable 

Brightness Input 

Indicator

Variable 

Brightness Output 

Indicator

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Summary of Contents for APD 6380

Page 1: ... For APD 6380 specify if UL version is required Order options and accessories as required Order D versions for operation on low voltage power How to Order Free factory setup Please specify on your order Input range Output range AC Input Ranges Field selectable ranges via switch settings Voltage 0 40 mVAC to 0 300 VAC Current 0 4 mAAC to 0 200 mAAC Measurements are true RMS Input Impedance Voltage ...

Page 2: ... VE38V VE31V VE36V VE39V VE32V VE37V VE33V VE34V VE35V VE30I VE38I VE31I VE36I VE39I VE32I VE37I VE33I 0 20 V VF20V VF28V VF21V VF26V VF29V VF22V VF27V VF23V VF24V VF25V VF20I VF28I VF21I VF26I VF29I VF22I VF27I VF23I 0 25 V VC20V VC28V VC21V VC26V VC29V VC22V VC27V VC23V VC24V VC25V VC20I VC28I VC21I VC26I VC29I VC22I VC27I VC23I 0 40 V V460V V468V V461V V466V V469V V462V V467V V463V V464V V465V ...

Page 3: ... generally easier to select ranges before installation The module side label lists common ranges See the model serial number label for module information options or if a custom range was specified It may also be possible to use the next highest setting and trim the output signal with the zero and span potentiometers Switch A Set to V for voltage input Switch B Input range Switch C Input range Swit...

Page 4: ... that can be used as a diagnostic aid during initial start up or troubleshooting When released the output will return to normal The Test Cal potentiometer is factory set to approximately 50 output It can be adjusted to set the test output from 0 to 100 of the output span Press and hold the Test button and adjust the Test Cal potentiometer for the desired output level Operation The APD 6380 accepts...

Reviews: