ADJUSTMENT

OF

DOOR MOVEMENTS

a)

I

om

8

I.

(;]11

-

-

Se

Buttons:

a) Se button

This button is used to call

control points

0... 28 onto

the display. With the light on the digital

display, press the Se button for at least

3 seconds enabling yellow Adjustment LEDto light.

Digit

1 with a

signal dot

appears on the right-hand side

digital display to indicating the first control point.
Control points 0... 28 can now be addressed by

pressing the Se button. Should you wish to
reverse the control point, press the S/A- button.

I

o

b)

~rn'

° -

°

_I.

S/A-

~-)

-------

Adj

b) S/A- button

This button is used to select a lower control point

number from 0 ... 28, or to decrease the value in the

control point.

c) Adj button

When the desired control point has been selected with
the Se button, pressing the Adj

button validates the

control value

and flashes on the

display.

The Adjustment LED will also flash, except for a sealed

control point.

The signal dot

disappears from the right-

hand side display.

NOTE!The control setting of sealed control points can

only be changed after first pressing the Adj

button for at least 5 seconds following which the

Adjustment LED will flash.

The control setting can be increased one step at a time

by pressing the Adj button, and decreased by

the S/A- button.

When the desired control setting is shown on the
display, press the Se button. This will store the

control setting in memory and the digit indicating the

number of the

next

control point appears on the

display. The Adjustment LEDwill remain lit up but will
cease flashing.

-

10

-~----

-

---.

-------------

Summary of Contents for DA400

Page 1: ..._ _ ABLOY ABlOyID DA400 Swing door operator _ _ OJ f I I I I I I I y l I I I _V __ ER_SIO_N_1 _5 _ 0 All ASSA A810Y Group co y...

Page 2: ...res running to the switch carries 5 V and the other the ground level of the control unit when the switch is open 1 Sequencing 2 1 sequence control 7 2 d 2 Outside impulse inhiblV 2 3 Main power state...

Page 3: ...iately on a impulse The contacts of a impulse device must be potentialily free and have a normally open function 5 Inside impulse The door opens after preset delay 0 15 sec 6 Safety sensor The sensor...

Page 4: ...using separate program switch LEO X4 EJ Pulse counter 27 I red 26 I loci 25 24 k 23 I 22 I leek 21 I red 20 lId 19 CONTROL UNIT Permanent wiring shall be employed if required by local codes Permanent...

Page 5: ...ter has three sensors Two count the pulses and the disk direction the other senses the perimeter of the disk n Adjusting the door closed position 1 Mount the operator and fit the arm When closing the...

Page 6: ...selector e g 0 MANUAL 1 AUTOor 2 OPEN The right hand display section indicates the status of opening pulses the safety sensor and the locking circuit Program selector I pulse display status I ro C Ix...

Page 7: ...Adjustment button When the desired control point has been selected with the Selection button pressing the Adjustment button validates the control value and flashes on the display The Adjustment LEDwil...

Page 8: ...speed 40 _ _ _ _ n 1 3 60 Door open position 48 1 __ _ _ _ I C 0 60 ClosIng direction Starting point of final speed 10 1 __ _ _ J 1 10 Operator s force Sealed 5 L c _ _ _ _ _ LI 0 15 Delay time for i...

Page 9: ...__ _ D 8J 1 or 0 Operation of lock control relay a _ _ DB 1 or 0 Closing direction Safety feature a I I B jJ 0 10 Hold open force a _ _ 8fl 0 10 Pressure closed before opening a JLJ laB _ _ f 1 10 Lo...

Page 10: ...iately but the door is delayed I LJ 0 in opening to accommodate for the locks release 0 I CJN CJ Adjust the opening speed so that the safety feature is not activated Adjust the final speed in order so...

Page 11: ...o close the door at intervals of 60 seconds 8 corresponds to minimum sensitivity 1 on 0 off Power assisted manual opening will function when the door operator is set to automatic mode DB 1 Standard ar...

Page 12: ...open The opening delay of the second door is adjusted in control point 4 Note The inside impulse connection is not operational 3 Interlock controlled doors Used in two door following each other The fi...

Page 13: ...e counter indicates number of openings The fixed obsticles in safety sensor zone can be excluded by adjusting the area smaller than the door open position Dlspalys the program version 0 DA400 Europe 1...

Page 14: ...y is connected put the battery operation ON If battery operation Is not selected the battery will not be charged Adding batteries Fire door use DA131 1 pes 12V 2 2Ah battery adapter Full battery back...

Page 15: ...hould be replaced The test made by the operator The battery is loaded with 0 4 A test load for a 30 second period If the battery voltage drops under U S V the battery is found unsuitable a red LEDflas...

Page 16: ...In 24 hour period the battery should be replaced The test made by the operator The battery is loaded with 0 4 A test load for a 30 second period If the battery voltage drops under 11 5 V the battery i...

Page 17: ...t made by the operator The battery is loaded with 0 8 A test load for a 10 second period If the battery voltage drops under 23 V the battery is found unsuitable a red LEDflashes at the end of the oper...

Page 18: ...on 1 2 3 4 FUlEDETECTOR N C iN O relay output Fire detector input If the jumper is on the adapter requires N O output from the fire detector otherwise N e Battery alarm keep If the jumper is on the ba...

Reviews: