BATTERY OPERATION
24 V Full battery backup;
The operator and devices connected will operate during
a power failure. The operation time depends on number of openings and the current
draw of the devices fitted.
.
When battery backup use is chosen, the battery is checked by the operator and the
following should be noted:
BATTERYVOLTAGE
15 V
26 V
()
Battery operation is
set to 12V battery
The battery is tested If the
voltage rises above 26 V it
is operational.
If
the voltage does not rise
above 26 V in 24 hour period,
the battery should be
replaced
The operator tests
the battery
The test made by the operator:
The battery is loaded with 0.8 A test load for a
10 second period. If the battery voltage drops under 23 V, the battery is
found unsuitable = > a red LED flashes at the end of the operator indicating this
state.
During power failure .. ,.
The operator and devices connected will operate normally. The red LEDstarts
to blink.
WHEN BATTERYVOLTAGE DROPS UNDER
17 V
20 V
The operator halts
Low-energy state:
The door is opened manually
and the operator closes door.
When power failure ends ....
The red LED stops blinking.If the operator stays in low-energy state, one manual
opening is required to re-enegise the operator to chosen program selector mode.
Note I In battery use the continious load in 24V output must not exceed 200 mA.
Do not use the Lock-up force (control point 11).