Abloy DA400 Manual Download Page 17

BATTERY OPERATION

24 V Full battery backup;

The operator and devices connected will operate during

a power failure. The operation time depends on number of openings and the current

draw of the devices fitted.

.

When battery backup use is chosen, the battery is checked by the operator and the
following should be noted:

BATTERYVOLTAGE

15 V

26 V

()

Battery operation is

set to 12V battery

The battery is tested If the

voltage rises above 26 V it
is operational.

If

the voltage does not rise

above 26 V in 24 hour period,
the battery should be
replaced

The operator tests
the battery

The test made by the operator:

The battery is loaded with 0.8 A test load for a

10 second period. If the battery voltage drops under 23 V, the battery is

found unsuitable = > a red LED flashes at the end of the operator indicating this

state.

During power failure .. ,.

The operator and devices connected will operate normally. The red LEDstarts
to blink.

WHEN BATTERYVOLTAGE DROPS UNDER

17 V

20 V

The operator halts

Low-energy state:

The door is opened manually

and the operator closes door.

When power failure ends ....

The red LED stops blinking.If the operator stays in low-energy state, one manual

opening is required to re-enegise the operator to chosen program selector mode.

Note I In battery use the continious load in 24V output must not exceed 200 mA.

Do not use the Lock-up force (control point 11).

25

Summary of Contents for DA400

Page 1: ..._ _ ABLOY ABlOyID DA400 Swing door operator _ _ OJ f I I I I I I I y l I I I _V __ ER_SIO_N_1 _5 _ 0 All ASSA A810Y Group co y...

Page 2: ...res running to the switch carries 5 V and the other the ground level of the control unit when the switch is open 1 Sequencing 2 1 sequence control 7 2 d 2 Outside impulse inhiblV 2 3 Main power state...

Page 3: ...iately on a impulse The contacts of a impulse device must be potentialily free and have a normally open function 5 Inside impulse The door opens after preset delay 0 15 sec 6 Safety sensor The sensor...

Page 4: ...using separate program switch LEO X4 EJ Pulse counter 27 I red 26 I loci 25 24 k 23 I 22 I leek 21 I red 20 lId 19 CONTROL UNIT Permanent wiring shall be employed if required by local codes Permanent...

Page 5: ...ter has three sensors Two count the pulses and the disk direction the other senses the perimeter of the disk n Adjusting the door closed position 1 Mount the operator and fit the arm When closing the...

Page 6: ...selector e g 0 MANUAL 1 AUTOor 2 OPEN The right hand display section indicates the status of opening pulses the safety sensor and the locking circuit Program selector I pulse display status I ro C Ix...

Page 7: ...Adjustment button When the desired control point has been selected with the Selection button pressing the Adjustment button validates the control value and flashes on the display The Adjustment LEDwil...

Page 8: ...speed 40 _ _ _ _ n 1 3 60 Door open position 48 1 __ _ _ _ I C 0 60 ClosIng direction Starting point of final speed 10 1 __ _ _ J 1 10 Operator s force Sealed 5 L c _ _ _ _ _ LI 0 15 Delay time for i...

Page 9: ...__ _ D 8J 1 or 0 Operation of lock control relay a _ _ DB 1 or 0 Closing direction Safety feature a I I B jJ 0 10 Hold open force a _ _ 8fl 0 10 Pressure closed before opening a JLJ laB _ _ f 1 10 Lo...

Page 10: ...iately but the door is delayed I LJ 0 in opening to accommodate for the locks release 0 I CJN CJ Adjust the opening speed so that the safety feature is not activated Adjust the final speed in order so...

Page 11: ...o close the door at intervals of 60 seconds 8 corresponds to minimum sensitivity 1 on 0 off Power assisted manual opening will function when the door operator is set to automatic mode DB 1 Standard ar...

Page 12: ...open The opening delay of the second door is adjusted in control point 4 Note The inside impulse connection is not operational 3 Interlock controlled doors Used in two door following each other The fi...

Page 13: ...e counter indicates number of openings The fixed obsticles in safety sensor zone can be excluded by adjusting the area smaller than the door open position Dlspalys the program version 0 DA400 Europe 1...

Page 14: ...y is connected put the battery operation ON If battery operation Is not selected the battery will not be charged Adding batteries Fire door use DA131 1 pes 12V 2 2Ah battery adapter Full battery back...

Page 15: ...hould be replaced The test made by the operator The battery is loaded with 0 4 A test load for a 30 second period If the battery voltage drops under U S V the battery is found unsuitable a red LEDflas...

Page 16: ...In 24 hour period the battery should be replaced The test made by the operator The battery is loaded with 0 4 A test load for a 30 second period If the battery voltage drops under 11 5 V the battery i...

Page 17: ...t made by the operator The battery is loaded with 0 8 A test load for a 10 second period If the battery voltage drops under 23 V the battery is found unsuitable a red LEDflashes at the end of the oper...

Page 18: ...on 1 2 3 4 FUlEDETECTOR N C iN O relay output Fire detector input If the jumper is on the adapter requires N O output from the fire detector otherwise N e Battery alarm keep If the jumper is on the ba...

Reviews: