37
7. Specifications
Model
6000 VA
10000 VA
INPUT
Voltage Window
160~280Vac
(1Φ) *
Frequency
45 ~ 65 Hz
Phase/Wire
Single, Line + N Ground
Power Factor
Up to 0.99 at 100% Linear Load
Current THD (100% linear
load)
<6%
OUTPUT
Voltage Window
220/230/240Vac Selectable **
Voltage Adjustment
±
0%;
±
1%;
±
2%;
±
3%
Voltage Regulation
±
1%
Capacity **
6000VA / 4800W
10000VA / 8000W
Rated Power Factor
0.8 Lagging
Wave Form
Sine Wave, THD<3%(no load to full load)
Frequency Stability
±
0.2%(Free Running)
Frequency Regulation
±
1%;
±
3%
Transfer Time
0ms
Load Crest Factor
3:1 acceptable
Efficiency(AC to AC, Normal)
≥ 90%
Autonomy
≥6 min.
≥4 min.
DC Start
Yes
BATTERY
Type
Sealed Lead Acid
Maintenance Free
12V/7AH
Sealed Lead Acid
Maintenance Free
10KVA: 12V/9AH
Quantity
20pcs
Voltage
240Vdc
Recharge Time
4 hours to 90%
5 hours to 90%
DISPLAY
Status On LED + LCD
Line Mode, Backup Mode, ECO Mode, Bypass
Supply, Battery Low, Battery Bad/Disconnect,
Overload, Transferring with interruption & UPS
Fault.
Readings on LCD
Input Voltage, Input Frequency, Output Voltage,
Output Frequency, Load Percentage, Battery
Voltage & Inner Temperature.
Self-Diagnostics
Upon Power-on, Front Panel Setting &
Software Control, 24-hour routine checking