Step 6:
Use the flip-switch on the battery pack to set the following items:
1. Communication ID:
Set the battery pack ID from bottom to top; the ID must be set starting from 1 and must be
consecutive numbers. The maximum ID is 6.
※
Please do not set the ID as nonconsecutive numbers, such as 1, 2, 4 or starting from
numbers other than 1, such as 2, 3, 4.
2. Terminating battery pack
The terminating battery pack only needs to be turned on for the battery pack with the last
communication ID.Its goal is to increase the stability for communication.
Please refer to the explanations in the figure below for setting methods of the communication ID
and terminal resistance. Switching the flip-switch to the bottom means Off and switching it to the top
means On. Please refer to the ID setting table for ID settings.
Flip-switch
Terminating
resistance
1 (On)
0 (Off)
ID setting switch
ID setting switch