5.  CONFIGURATION
The  BA648CF-P  8  variable  PROFIBUS  PA
indicator  may  be  configured  as  a  fieldbus  node  or
as  a  fieldbus  listener.      When  used  as  a  fieldbus
node  the  indicator  is  configured  via  the  fieldbus
host  although  the  instrument  address  may  be
entered via  the front  panel  push  buttons  using  the
menu  shown  in  Fig  4.      For  detailed  node
conditioning  information  please  refer  to  the  BEKA
PROFIBUS PA Display – Fieldbus Interface Guide
which may be downloaded from the BEKA website
www.beka.co.uk

As a fieldbus listener, the BA648CF-P is not visible
to the fieldbus host and can only be configured via
the  front  panel  push  buttons  using  the  menu
shown in Fig 6.

Throughout  this  manual  the  BA648CF-P  push
buttons  are  identified  P    E   

 

  and  legends

displayed  by  the  instrument  are  shown  within
inverted commas  e.g. ‘CodE’ and ‘Enb’.

5.1  Configuration menus
The  configuration  menus  are  separated  into  two
sections, fieldbus node and fieldbus listener.   Both
contain  the  ‘tYPE’  function  that  enables  transfer
between  the  two.      Unless  otherwise  requested
when  ordered,  all  PROFIBUS  PA  BA648CF-P
instruments  are  supplied  as  a  fieldbus  node  with
default configuration but can easily be reconfigured
on-site.

5.2 Node configuration menu
The  node  configuration  menu  is  shown  in  Fig  4.
Access to the menu is obtained by operating the P
and  E  buttons  simultaneously.    If  the  BA648CF-P
is  not  protected  by  an  access  code  the  first
parameter  'Addr’  will  be  displayed.    If  the
instrument is protected by an access code, ‘CodE’
will  be  displayed  first.    Pressing  P  will  allow  the
four  digit  security  code  to  be  entered  digit  by  digit
using the 

 or 

 button to adjust the flashing digit

and P to move control to the next digit.  When the
correct  code  has  been  entered,  pressing  E  will
cause  the  first  parameter  ‘Addr’  to  be  displayed.
If  an  incorrect  code  is  entered,  or  no  button  is
pressed  for  ten  seconds,  the  BA648CF-P  will
automatically return to the display mode.

5.2.1 Enter fieldbus address      ‘Addr’
This  function  enables  the  fieldbus  address  of  the
BA648CF-P  to  be  entered  via  the  push  buttons.
Select  ‘Addr’  in  the  node  menu  using  the 

  or 

button and press P to  enter the function.  This  will
reveal the existing three digit decimal address with
the  left  hand  digit  flashing  which  may  be  changed
by operating the 

 or 

 button.

When  set  as  required  operating  the  P  button  will
transfer  control  to  the  next  digit  that  may  be
adjusted in the same way.  When all digits are set
as  required  operating  the  E  button  will  enter  the
new  address  and  the  indicator  will  restart  in  the
display  mode  after  completing  the  initialisation
sequence.    If  the  address  is  not  changed,
operating the E button will return the display to the
‘Addr’ prompt in the node configuration menu.

5.2.2  Access code for configuration menu
          ‘CodE’
Access  to  the  node  configuration  menu  may  be
protected  by  a  four  digit  security  code  which  must
be  entered  to  gain  access.    New  instruments  are
supplied  configured  with  the  default  code  0000
which 

disables 

this 

protection 

and 

allows

unrestricted access to the configuration menu.

To  enter  a  new  access  code  select  ‘CodE’  in  the
node configuration menu by operating the 

 or 

button.      To  enter  the  function  press  P  which  will
reveal  the  current  access  code  with  one  digit
flashing. The code may be changed using the 

 or

  button  to  adjust  the  flashing  digit  and  the  P

button to move control to the next digit.  When the
required code has been selected, press E to enter
the selection and return to the ‘CodE’ prompt in the
configuration menu.    The revised access code will
be activated when the transmitter is returned to the
display mode.

If  the  access  code  is  lost  please  contact  BEKA
associates.

5.2.3  Change from node to listener   ‘tYPE’
This  function  enables  the  instrument  to  be
changed from a fieldbus node to a fieldbus listener.
Select ‘tYPE’ in the node configuration menu using
the 

  or 

  button.  To  enter  the  function  press  P

which will show that the instrument is configured as
a  fieldbus  node,  to  change  to  a  fieldbus  listener
press  the 

  or 

  button  which  will  toggle  the

display to ‘LStnr’   To prevent accidental  changes
this request must be confirmed by operating  the P
button  and  entering    ‘5urE’.    The  instrument  will
display ‘0000’ with the first digit flashing, using the

 or 

 button set the flashing digit to ‘5’ and press

the P button to move control to the next digit which
should be set to ‘u’.  When the four letters of ‘5urE’
have  been  entered,  operating  the  E  button  will
cause  the  instrument  to  restart  as  a  fieldbus
listener in the display mode.

CAUTION

All  the  instrument’s  node  configuration
information  will  be  lost  when  it  is
changed  from  a  fieldbus  node  to  a
fieldbus listener.

Summary of Contents for BEKA associates BA648CF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA648CF P ...

Page 2: ...hill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0 1224 725999 Email ab able co uk Internet www able co uk e procurement www 247able com Registered in England No 01851002 VAT No GB 417 2481 61 ...

Page 3: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2 ...

Page 4: ...t parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset the listener to factory defaults 6 ...

Page 5: ...on label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA648CF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide wh...

Page 6: ...r panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite sides of the instrument and tighten until the instrument is secure Four clips are required to achieve an IP66 seal between the instrument enclosure and the panel c Connect the panel wiring to the rea...

Page 7: ...nd digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed o...

Page 8: ...ddresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the seg...

Page 9: ...7 ...

Page 10: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 11: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ente...

Page 12: ...y mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b ...

Page 13: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA648CF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 14: ...ration after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648CF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause of the failure If this procedure does not reveal the cause of the fault it is recommen...

Page 15: ...d a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus Interface Guide The BEKA PROFIBUS PA Display Fieldbus Interface Guide contains commissioning information for the BA648CF A copy may be requested from the BEKA sales office or downloaded from the BEKA...