ABLE BEKA associates BA648CF-P Installation & Maintenance Instructions Manual Download Page 13

11

The ‘SCALE’ function may be selected from within
the edit sub-menu by operating the 

 or 

 button.

To enter the function press P which will display the
‘GAin’  sub-function,  pressing  P  again  will  reveal
the  existing  gain  with  one  digit  flashing.  This
flashing  digit may  be  changed  by  operating  the 

or 

▲ button; when adjusted the 

P button will move

control  to  the  next  digit  or  to  the  decimal  point
which can be positioned using the 

 or 

 button.

When  ‘GAin’  has  been  set  to  the  required  value
operating  the  E  button  will  enter  the  selection  and
return  to  the  ‘GAin’  prompt  in  the  sub-menu  from
where  the  ‘oFFSt’  function  can  be  selected  using
the 

 or 

 button.

To  enter  the  ‘oFFSt’  function  press  P  which  will
reveal  the  existing  offset  with  one  digit  flashing.
Again  the  flashing  digit  may  be  changed  by
operating the 

 or 

  button and the P  button  will

move  control  to  the  next  digit  or  to  the  decimal
point.  When  ‘oFFSt’  has  been  set  to  the  required
value operating the E button will enter the selection
and  return  to  the  ‘oFFSt’  prompt  in  the  sub-menu.
Three  operations  of  the  E  button  will  return  to  the
‘Edit’ function in the main configuration menu.

5.4.11 Access code for listener configuration
           menu           ‘CodE’
Access  to  the  listener  configuration  menu  may  be
protected  by  a  four  digit  security  code  which  must
be  entered  to  gain  access.    New  instruments  are
supplied  configured  with  the  default  code  0000
which 

disables 

this 

protection 

and 

allows

unrestricted access to the configuration menu.

To  enter  a  new  access  code  select  ‘CodE’  in  the
configuration  menu  by  operating  the 

  or 

button.      To  enter  the  function  press  P,  this  will
reveal  the  current  access  code  with  one  digit
flashing. The code may be changed using the 

 or

  button  to  adjust  the  flashing  digit  and  the  P

button to move control to the next digit.  When the
required code has been selected, press E to enter
the selection and return to the ‘CodE’ prompt in the
configuration menu.    The revised access code will
be activated when the transmitter is returned to the
display mode.

If  the  access  code  is  lost  please  contact  BEKA
associates.

5.4.12    Change  from  fieldbus  listener  to
fieldbus node   ‘tYPE’
This  function  enables  the  BA648CF-P  to  be
conditioned  as  a  fieldbus  node  or  as  a  fieldbus
listener.  To change the  function  of  the  instrument
select  ‘tYPE’  in  the  listener  configuration  menu
using  the 

  or 

  button  and    press  P  to  enter

which will show that the instrument is configured as
a fieldbus listener.

To  change  to  a  fieldbus  node  press  the 

  or 

button  which  will toggle the display to  ‘nodE’.      To
prevent  accidental  changes  this  request  must  be
confirmed  by  operating  the  P  button  and  entering
‘5urE’.    The  instrument  will  display  ‘0000’  with  the
first digit flashing, using the 

 or 

 button set the

flashing digit to ‘5’ and press the P button to move
control to the next digit  which  should  be  set  to  ‘u’.
When the four letters of ‘5urE’ have been entered,
operating  the  E  button  will  result  in  the  instrument
restarting in the display mode as a fieldbus node.

CAUTION

All the instrument’s listener configuration
information  will  be  lost  when  it  is
changed  from  a  fieldbus  listener  to  a
fieldbus node.

5.4.13  Reset the listener to factory defaults
            ‘rESEt’
The  BA648CF-P  listener  may  be  reset  to  the
factory defaults that are shown below:

Security Code

0000 (disabled)

For each of the eight inputs:

Decimal point

XXX.XX

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

To  reset  the  BA648CF-P  listener  select  ‘rESEt’  in
the  configuration  menu  by  operating  the 

  or 

button.      To  enter  the  function  press  P,  this  will
reveal  ‘0000’  with  the  left  hand  digit  flashing.    To
prevent accidental use of this function, ‘5urE’ must
be  entered  to  confirm  that  the  instrument  is  to  be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the P button to move control to the next
digit  which  should  be  set  to  ‘u’.    When  the  four
letters of ‘5urE’ have been entered operating the E
button  will  reset  the  BA648CF-P  to  the  factory
defaults.      Any  existing  configuration  and
addresses will be lost when the listener is reset.

Summary of Contents for BEKA associates BA648CF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA648CF P ...

Page 2: ...hill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0 1224 725999 Email ab able co uk Internet www able co uk e procurement www 247able com Registered in England No 01851002 VAT No GB 417 2481 61 ...

Page 3: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2 ...

Page 4: ...t parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset the listener to factory defaults 6 ...

Page 5: ...on label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA648CF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide wh...

Page 6: ...r panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite sides of the instrument and tighten until the instrument is secure Four clips are required to achieve an IP66 seal between the instrument enclosure and the panel c Connect the panel wiring to the rea...

Page 7: ...nd digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed o...

Page 8: ...ddresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the seg...

Page 9: ...7 ...

Page 10: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 11: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ente...

Page 12: ...y mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b ...

Page 13: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA648CF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 14: ...ration after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648CF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause of the failure If this procedure does not reveal the cause of the fault it is recommen...

Page 15: ...d a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus Interface Guide The BEKA PROFIBUS PA Display Fieldbus Interface Guide contains commissioning information for the BA648CF A copy may be requested from the BEKA sales office or downloaded from the BEKA...

Reviews: