Part II - Adjustments

Tools Needed

Models 126, 134, S126B, S134B:  

3/16" & 1/4" open-end wrenches

Models 136-160, S136B, S160B, 680:

  5/8" open-end wrench

Models 258-274, 354-364:

  11/16" open-end wrench

Models 218-230: 

 1/4" open-end wrench

Models 610-614:

  3/16" open-end wrench

Pressure Models

For  set  point  adjustment,  connect  unit  to  a  calibrated 

pressure  source.  Remove  cover  and  gasketing.  The 

adjusting  screw,  labeled  “A”  in  Figures  1  &  2,  is  located 

beneath  the  switch  and  is  turned  to  adjust  the  set  point. 

Using the appropriately sized open-end wrench (see Tools 

Needed  above),  turn  the  adjustment  screw  towards  the 

left  (clockwise)  to  increase  set  point  or  towards  the  right 

(counter-clockwise) to decrease set point.

Vacuum Models

For  set  point  adjustment,  connect  unit  to  a  calibrated 

source.  Remove  cover  and  gasketing.  The  adjusting 

screw, labeled “A” in Figures 1 & 2, is located beneath the 

switch  and  is  turned  to  adjust  the  set  point.  Using  a  1/4” 

open-end  wrench,  turn  the  adjustment  screw  towards  the 

right (counter-clockwise) to increase set point (towards full 

vacuum)  or  towards  the  left  (clockwise)  to  decrease  set 

point (towards 0 psig). 

NOTE

: For models 126-134 & S126B-S134B, use 3/16” open-end 

wrench to keep item B (Figure 2) from turning.

Figure 1: Models 136-160, S136B-S160B, 258-274, and 354-364

Figure 2: Models 126, 134, S126B, S134B, 218-230,

                         610-614, 680
NOTE:

 Picture shows adjustable deadband switch option

Adjustable Deadband Switch,

J6D Models and Option 1520

Units  with  this  option  are  equipped  with  a  special  snap 

switch that allows the deadband to be manually adjusted. 

To adjust the deadband, turn the adjustment wheel on the 

underside of the switch (item C in Figure 2), using the switch 

mounting  screw  on  the  right  as  an  index.  As  the  letters 

advance, the deadband widens.

Manual Reset Switches, 1530 Option

Units with this option incorporate a snap switch that, when 

activated, remains tripped until the pressure drops and the 

reset button (located on top of the enclosure) is manually 

depressed to reset the switch.

Replace  cover  when  all  operations  are  complete  and 

before using.

��������������

���������

��������

�������������������

��

�������

��

��

� �

��

��������

����������

�������������������

�������

������������������������
������������������������
����������������������������
���������������

�������������������

�������������������������
��������������������������

���������������������������

�����������������������

��������������������������

���������������������������

IM6-02