GENERAL

BEFORE  INSTALLING,  CHECK  THE  SENSOR 

MODEL  SELECTED  FOR  COMPATIBILITY  TO 

THE  PROCESS  MEDIA  IN  CONTACT  WITH  THE 

SENSOR AND WETTED PARTS.

J6 pressure switches are activated when a bellows or piston 

sensor  responds  to  a  pressure  change.  This  response 

actuates  a  single  snap-action  switch,  converting  the 

pressure signal into an electrical signal.

Set point may be varied by turning the internal adjustment 

screw according to procedures outlined below.

Part I - Installation

Tools Needed

 

-Adjustable wrench

- Flatblade screwdriver

MOUNTING

J6  pressure  switches  may  be  mounted  and  operated  in 

any  position.  They  may  be  surface  mounted  via  the  two 

mounting ears on either side of the enclosure, or mounted 

directly to a rigid pipe by using the pressure connection.

LOCATE THE UNIT WHERE VIBRATION, SHOCK 

AND  AMBIENT  TEMPERATURE  CHANGES  ARE 

MINIMAL.  SHOULD  THE  UNIT  BE  INSTALLED 

WHERE  CONDENSATION  IS  EXPECTED,  VERTICAL 

MOUNTING IS RECOMMENDED.

NEVER USE THE ENCLOSURE FOR LEVERAGE 

TO 

HAND 

TIGHTEN 

THE 

PRESSURE 

CONNECTION.  ALWAYS  USE  A  WRENCH  TO 

TIGHTEN  THE  PRESSURE  CONNECTION  TO  THE 

PIPE. 

On models supplied with an external manual reset button, 

be sure to leave sufficient finger space over the reset button 

for the operator to reset the switch.

WIRING

WIRE  IN  ACCORDANCE  WITH  LOCAL  OR 

NATIONAL  CODES.  BE  SURE ALL  LIVE  SUPPLY 

CIRCUITS  ARE  DISCONNECTED  BEFORE 

WIRING  THE  CONTROL.  MAXIMUM  WIRE  SIZE  #14 

AWG.

Remove  the  four  screws  retaining  the  cover  and  cover 

gasket. A 1/2” NPT conduit connection is provided on the 

upper  left  hand  side  of  the  enclosure.  The  three  switch 

terminals are clearly labeled common, normally open and 

normally closed.

If lead wires are supplied, color coding is as follows:

SPDT

Common

Violet

Normally Open

Blue

Normally Closed

Black

A threaded grounding boss, tapped #10-32, is provided in 

the lower left corner of the enclosure. Keep the wires as 

short as possible to prevent interference with the plunger, 

manual  reset  button  and,  when  provided,  the  adjustable 

differential switch wheel.

6 Series

Pressure Switch

IM6-02