Mains and Battery LEDs 

The 

swampfox

’s internal battery charger charges the internal battery, or an external 

12V sealed lead acid battery (6Ah or more) connected to the 

EXT BATT/DC 

connector. While power is present, the 

MAINS

 and 

BATT

 indicators show 

swampfox

’s 

state: 

Mains LED  Battery LED 

swampfox power, charger and battery status 

Green 

Green 

Normal 

POWER

 energized, battery OK, not charging 

Red 

Green 

Backup 

POWER

 not energized, running from battery 

Either 

Red 

Battery Low 

Battery voltage low (or battery disconnected) 

Unlit 

Green 

12V Powered 

Powered through 

EXT BATT/DC

 

Green 

Green flashing  Charging 

 

Green 

Red flashing 

Charge Failure 

Mains failed while charging, or faulty battery 

 

 

Other Front Panel Items 

The 

COMMS

 LED illuminates red when 

swampfox

 cannot communicate with a 

master. 

The 

DISPLAY

 button turns the front panel indicators on and off. The ready LED is 

always enabled. 

The 

ADDRESS SWITCHES

 set 

swampfox

’s three digit RTU address. 

 

 

 

All 

GND

 pins, the 

EXT BATT/DC

 connector negative pin, and the antenna shield, are 

all connected inside the 

swampfox

 

 

swampfox only examines the address 
switches when it starts up or is reset 

IG-619-2.2-2015-Mar 

Installation Guide 

Summary of Contents for swampfox SF1

Page 1: ...Pump Station Controller Models SF1 and SF3 Installation Guide ...

Page 2: ...pply or External Battery 12V BATT or SUPPLY An external power option can be installed in swampfox that can provide a switched 13 8V supply up to 1A through pins 2 and 3 of the power connector as shown This can be used to power an external device such as a cellular modem With the 12V DC powering arrangement a 12V DC supply is fed into the EXT BATT DC connector This connection is also used to charge...

Page 3: ... For RTUs with a d suffix the Digital Inputs are internally pulled up to the 12V rail The are activated by pulling the input to GND via a switch or relay contact Analog Inputs General Description Inactive LED off Active LED on Maximum Resistance Positive 4 20mA current 0 4mA 4 20mA 5V 40mA 120Ω to GND 100 mA MAX 3 1 2 0 GND 24V A INs Analog Inputs Internally Powered 4 20 mA TRANSDUCERS 3 1 2 0 GND...

Page 4: ...ally Powered 3 1 2 0 4 GND 12V FIELD SUPPLY The pin with the diode symbol must be connected to the positive rail from which any inductive loads are powered to protect swampfox against back EMF Security I O The fail safe alarm is an open collector which can carry 50mA up to 30V and can drive a relay coil directly INHIBIT TAMPER ALARM GND Door Switch Key Operated Switch Fail safe Alarm see text Secu...

Page 5: ...t This is a standard 100 base T Ethernet port which is operational when the appropriate firmware is installed External Radio Connections These connections are applicable only when no internal radio is fitted 1 8 RJ45 Pins Always use best radio frequency engineering practices for all radio and antenna installation Dir Name 1 sf 12V 2 2 1 sf COut2 3 1 sf CIn2 4 sf COut1 5 sf CIn1 6 sf TxD 7 sf RxD 8...

Page 6: ...iving RF on it s channel RX DATA Yellow Shows the data being received by swampfox PTT Yellow swampfox is transmitting on the radio channel TX DATA Yellow Shows the data being transmitted by swampfox A short blink is about 0 1 seconds A long blink is about 0 5 seconds Ready LED and Reset Ready LED indication swampfox operating state Green Normal swampfox is operating normally Red Defect Hardware or...

Page 7: ...tage low or battery disconnected Unlit Green 12V Powered Powered through EXT BATT DC Green Green flashing Charging Green Red flashing Charge Failure Mains failed while charging or faulty battery Other Front Panel Items The COMMS LED illuminates red when swampfox cannot communicate with a master The DISPLAY button turns the front panel indicators on and off The ready LED is always enabled The ADDRE...

Page 8: ...ox 27 497 Wellington New Zealand Phone 64 4 385 6611 Fax 64 4 3856848 Document Number IG 619 2 2 2015 Mar Products Covered SF1 and SF3 all variants Revision Number 2 2 Revision date 15 March 2015 swampfox and the logo are trademarks of Abbey Systems Ltd registered with the U S Patent and Trademark Office ...

Reviews: