Digital Inputs
General Description
Inactive, LED off
Active, LED on
Maximum
Resistance
Positive voltage-activated 0~+1.8V
+4.5~36.0V
±60V DC
12k
Ω to GND
11
1
10
0
+
12V
GND
D.INs
DRY
CONTACTS
(EG. RELAY
CONTACTS
SWITCHES)
Digital Inputs
– Externally Powered
FIELD
SUPPLY
By default Digital Inputs 0..3(, 12..15, 24..27 for SF3) are assigned to Pulse Counts
or Rates 0..3(, 4..11 for SF3). If Microlink-compatible pulse input mapping is
configured in Powerlink then Digital Inputs 9..6(, 21..18, 33..30) are mapped to
Pulses or Rates 0..3(, 4..11).
For RTUs with a
–d
suffix, the Digital Inputs are
internally pulled up to the 12V rail.
The are activated by pulling the input to
GND
via
a switch or relay contact.
Analog Inputs
General Description
Inactive, LED off
Active, LED on
Maximum
Resistance
Positive 4~20mA current
0~+4mA
+4~20mA
±5V ±40mA
120
Ω to GND
100 mA
MAX
3
1
2
0
GND
+
24V
A.INs
Analog Inputs
– Internally Powered
4~20 mA
TRANSDUCERS
3
1
2
0
GND
+
24V
A.INs
Analog Inputs
– Externally Powered
FIELD
SUPPLY
4~20 mA
TRANSDUCERS
IG-619-2.2-2015-Mar
2
Installation Guide
1
0
GND
D.INs
DRY
CONTACTS
(EG. RELAY
CONTACTS
SWITCHES)
Digital Inputs
– Internal Pullup
11
1
10
0
+
12V
GND
D.INs
DRY
CONTACTS
(EG. RELAY
CONTACTS
SWITCHES)
Digital Inputs
– Internally Powered
200 mA
MAX