1
) At operating voltages lower than the rated voltage, the same values fundamentally apply as for the rated voltage. Higher values on request.
(
2
) Individual unit without truck
M ED I U M VO LTAG E P R O D U C T S
33
10.2 Technical data
Circuit breakers for fixed installation
10.2.1 Performance data and weights
Rated voltage
kV
12
17.5
24
Rated frequency
Hz
50/60
50/60
50/60
Rated lightning impulse withstand voltage
kV
75
95
125
Rated power frequency withstand voltage
kV
28
38
50
Rated of rise of transient recovery voltage
kV/μs
0.34
0.42
0.47
Peak transient recovery voltage
kV
20.6
30
41
Rated operating sequence
O-3 min-CO-3 min-CO
Rated operating sequence for autoreclosing
O-0.3 s-CO-3 min-CO
Guideline values for function times:
kV
Closing time
approx. 16 ms
Opening time
approx. 10 ms
Arcing duration (at 50 Hz)
≤ 15 ms
Total opening time
≤ 25 ms
Minimum command time on closing
2 ms
Minimum command time on opening
2 ms
Breaker
type
Rated
voltage
Rated
current
Rated short-
circuit breaking
current symm. (
1
)
Pole
centres
Weight (
2
)
Permissible of
vacuum-interrupter
switching operations
VM1-T
kV
A
kA
mm
approx. kg
Figure 9/28 page 32
1212-20
12
1250
20
210
90/95
Diagram B
1220-20
2000
210/275
135/140
Diagram C
1212-25
12
1250
25
210
90/95
Diagram D
1220-25
2000
210/275
135/140
Diagram E
1720-25
17.5
2000
25
210/275
135/140
Diagram E
2412-20
24
1250
20
210
100/105
Diagram B
2412-25
24
1250
25
275
100/105
Diagram D