12. Technical
details
Weight 8
kg
Operating time
opening 3,5 s
closing 3,5 s
Operating angle
110°
1)
Contactors power requirement
3 W
Shortest control pulse
0,1 s
Operating voltage range
0,85...1,1 x U
n
Operating temperature range
-40...+55 °C
Terminal block size
6 mm
2
Motor
Rectifi ed DC, permanent magnet type
1) The operating angle can be redused by the
adjuster coupling (part of the adapter set)
For AC supplies, use rectifi ed motor current. Rated cur-
rent are the same as for a corresponding DC motor.
*) Rated current is the current under normal working conditions.
**) Max. current is the current for a stalled load from the motor ope-
rating device.
Motor operating device
Rated current
*)
Max.
current
**)
Protective mcb type
UEMC 40 K6_ - 24 VDC
12 A
40 A
- STO S271 K8
- 48 VDC
6 A
20 A
- STO S272 K4
- 60 VDC
5 A
17 A
- STO S272 K4
- 110 VDC
2 A
5.5 A
- STO S272 K2
- 125 VDC
2 A
5.5 A
- STO S272 K2
- 220 VDC
1 A
3 A
- STO S282 UCK1