30
TZIDC
DIGITAL POSITIONER | DS/TZIDC-EN REV. G
—
… Use in potentially explosive atmospheres
… IECEx
Type of protection Ex e – increased safety, Ex n – non-
sparking
Ex marking
IECEx Ex ec
Marking
Ex ec IIC T6 resp. T4...T1 Gc
Type Examination Test
Certificate
IECEx TUN 04.0015X
Type
Increased safety
Standards
IEC 60079
-
0, IEC 60079
-
7
IECEx Ex nA
Marking
Ex nA IIC T6 resp. T4...T1 Gc
Type Examination Test
Certificate
IECEx TUN 04.0015X
Type
IP rating ‘n’
Standards
IEC 60079
-
0, IEC 60079
-
15
Temperature Data
Temperature class
Ambient temperature Ta
T4 to T1
−35
to
+85
°C
T6*
−35
to
+50
°C*
* When using the ‘Plug-in module for digital feedback’ in temperature
class T6, the maximum permissible ambient temperature range is
−35
to
+35
°C.
Special conditions
•
For the ‘Feedback on the actuator position using
proximity switches (Pepperl & Fuchs SJ2
-SN
)’ circuit,
measures outside of the device must be implemented to
prevent an up-scale of the rated voltage by more than
40% in the event of transient disturbances.
• Only devices that are suited for operation in hazardous
areas of Zone 2 and the conditions prevailing at the place
of use may be connected to circuits in Zone 2
(manufacturer's declaration or certificate from the test
center).
• It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
• Only non-flammable gases must be used for pneumatic
power supply.
• Only use suited cable entries that meet the requirements
of EN
60079
-
7
or EN
60079
-
15
.
Electrical Data
In the ‘Increased safety Ex ec or non-sparking Ex nA’ type of
protection only for connection to a certified intrinsically safe
circuit.
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
(+11 /
-
12)
U = 9.7 V DC
I = 4 to 20
mA, max. 21.5
mA
Contact input
(+81 /
-
82)
U = 12
to 24 V DC
I = 4 mA
Switch output
(+83 /
-
84)
U = 11
V DC
Local communication
interface (LCI)
Only for connection to a programming device
using an ABB LCI adapter (Um ≤ 30 V DC)
outside the hazardous area.
The following modules may be operated as an option:
Current circuit (terminal) Electrical information (maximum values)
Feedback on the
actuator position using
proximity switches,
(Pepperl & Fuchs SJ2
-SN
)
(Limit1: +51 / −52),
(Limit2: +41 /
-
42)
U = 8.2
V (Ri approx. 1
kΩ)
Plug-in module for
digital feedback
(+51 /
-
52)
(+41 /
-
42)
U = 5
to
11 V DC
Plug-in module for
analog feedback
(+31 /
-
32)
U = 10
to 30 V DC
I = 4 to 20
mA, max. 21.5
mA
Summary of Contents for TZIDC
Page 1: ...ABB MEASUREMENT ANALYTICS DATA SHEET TZIDC Digital positioner...
Page 35: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 35 FM installation drawing No 901265 Page 1 of 5...
Page 37: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 37 Page 3 of 5...
Page 39: ...TZIDC DIGITAL POSITIONER DS TZIDC EN REV G 39 Page 5 of 5...