Ex relevant specifications
CI/TZIDC-200/210/220-EN TZIDC-200, TZIDC-210, TZIDC-220
EN - 29
7 Ex relevant specifications
Change from one to two columns
7.1
TZIDC-200
FM Approval HLC 8/02 3010829
Explosion Proof; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. C-D
Intrinsic Safety; enclosure 4X; T5, max. 82 °C
CL I, II, III; Div 1; Grp. A-B-C-D-E-F-G
Non-Incendive; enclosure 4X ; T4, max. 85 °C
CL I; Div 2; Grp. A-B-C-D
CL II, III; Div 2; Grp. F-G
Dust-Ignition Proof; enclosure 4X; T5, max. 82 °C
CL II, III; Div 1; Grp. E-F-G
CSA Certification 1393920
Explosion Proof; enclosure 4X; T5, max. 85 °C
CL I; Div 1; Grp. C-D
CL II; Div 1; Grp. E-F-G
CL III
Intrinsic Safety; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. A-B-C-D
CL II; Div 1; Grp. E-F-G
CL III
ATEX / GOST Russia /
GOST Ukraine
II 2G EEx d II C T4/T5/T6
Type-Examination Test
Certificate:
DMT 02 ATEX E 029 X
Type:
Flameproof enclosure
Device class:
II 2G (EEx ib IIC)
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
ATEX
II 2G EEx ib IIC T6
Type-Examination Test
Certificate:
TÜV 98 ATEX 1370 X
Type:
Intrinsically safe equipment
Device class:
II 2G (EEx ib IIC)
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 50 °C
T6: -40 °C < T
amb
< 35 °C
IECEx
Ex ib IIC T6
Type-Examination Test
Certificate:
IECEx TUN 04.0015X, Issue no.: 0
Type:
Intrinsic safety
Temperature class:
T4, T5, T6
Permissible ambient
temperature:
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 50 °C
T6: -40 °C < T
amb
< 35 °C
7.2
TZIDC-210
FM Approval HLC 7/04 3019164
Explosion proof; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. C-D
Dust ignition-proof; enclosure 4X; T5; max. 82 °C
CL II, III; Div 1; Grp. E-F-G
CSA Certification 1555690
Explosion proof; enclosure 4X
Temperature range: -40 … 85 °C
T5, max. 85 °C ; T6, max. 70 °C
CL I; Div 1; Grp. C-D
CL II; Div 1; Grp. E-F-G
CL III
ATEX / GOST Ukraine
II 2G EEx d II C T4/T5/T6
Type-Examination Test
Certificate:
DMT 02 ATEX E 029 X
Type: Flameproof
enclosure
Device class:
II 2G (EEx ib IIC)
Temperature class:
T4, T5, T6
Permissible ambient temperature: T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C
ATEX
II 2G EEx ia IIC T6
Type-Examination Test
Certificate:
TÜV 02 ATEX 1831 X
Type: Intrinsically
safe
equipment
Device class:
II 2G (EEx ia IIC)
Temperature class:
T4, T5, T6
Permissible ambient temperature: T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 55 °C
T6: -40 °C < T
amb
< 40 °C