Commissioning
CI/TZIDC-200/210/220-EN TZIDC-200, TZIDC-210, TZIDC-220
EN - 23
6 Commissioning
6.1
TZIDC-200
bieten
1.
Feed in pneumatic supply power
2.
Feed in electrical supply power
• Feed in setpoint current 4 ... 20 mA (ter11/-12)
3.
Check mount:
• Press and hold
, plus or until operating mode 1.3 (manual adjustment within
the sensor range) is displayed; release
• Press or to move the actuator into the mechanical end position; check the end
positions; rotation angle is displayed in degrees; for high-speed mode, press and
simultaneously
Recommended range:
- between -28 ... 28° for linear actuators
- between -57 ... 57° for rotary actuators
Minimum angle: 25°
4.
Run Autoadjust
For linear actuators
1)
:
• Press and hold down
until
is displayed; release the control button
• Press
again and hold down until the countdown ends
• Release
; this starts Autoadjust
For rotary actuators
1)
:
•
Press and hold down
until
is displayed; release the control button
•
Press
again and hold down until the countdown ends
•
Release
; this starts Autoadjust
If Autoadjust is successful, the parameters will be stored automatically and the positioner will
revert to operating mode 1.1.
If an error occurs during Autoadjust, the process will be terminated with an error message. If
this happens, press and hold down or for approximately three seconds. The unit will switch
to the operating level, mode 1.3 (manual adjustment within the sensor range). The mount is
checked and corrected if necessary. Autoadjust then runs again.
1) The zero position is determined automatically and saved during Autoadjust (counter-clockwise (CTCLOCKW) for
linear actuators and clockwise (CLOCKW) for rotary actuators).