Electrical
connections
CI/TTF300-X1
TTF300
EN - 15
4.2.3 TTF300 EX d models with standard cable gland
General information
Type Capri
ADE 1F
ISO
threads
Outer diameter of
cable
Material
816674 No. 4 M20 x 1,5
Ø 6 ... 8.5 mm
Nickel-plated brass or stainless steel
818674 No. 4 1/2“ NPT
Ø 6 ... 8.5 mm
Nickel-plated brass or stainless steel
816694 No. 5 M20 x 1,5
Ø 9 ... 12 mm
Nickel-plated brass or stainless steel
818694 No. 5 1/2“ NPT
Ø 9 ... 12 mm
Nickel-plated brass or stainless steel
Intended use
-
Group II Category 2, Zones 1 and 2 for gas, Zones 21 and 22 for dust, Exell, ExtD,
ExdIIC
≤
2,000 cm³
- Ingress protection IP 66 / 67, 10 bar
- LCIE 97 ATEX 6008 X certification
- Permanent operating temperature range: -40 ... 100 °C with neoprene gasket
- Only for fixed installations and non-reinforced cables with round and smooth plastic sleeves
and suitable outer diameters
- All applicable requirements as stipulated by EN 60079-14 must be observed
Installation instructions
The rings will harden at low temperatures. To make them soft, keep them at a temperature of
20 °C for 24 hours prior to installation. Before fixing them onto the cable gland, bend the rings to
ensure they are soft and flexible.
1. Check that a suitable cable is being used (i.e., check the mechanical resilience, temperature
range, creep resistance, resistance to chemicals, outer diameter, etc.).
2. Strip the cable in accordance with the table information.
Stripping for ADE 1F N
º
[4] / [5]
Position
[mm]
Ø C
8,5 / 12
A 40
B 12
3.
Check the outer sleeve for damage and soiling.
4. Insert the cable in the cable gland.
5.
Tighten the cable gland until the cable is firmly enclosed by the sealing ring. Do not tighten
the cable gland any more than 1.5 times the specified torques!
Minimum tightening torques for ADE N
º
[4],
[5] in Nm
Position
[4]
[5]
1 7,5
12,5
A00230
2
1
2 3 3