![ABB TTF200 Operating Instructions Manual Download Page 25](http://html.mh-extra.com/html/abb/ttf200/ttf200_operating-instructions-manual_4530025.webp)
TTF200
FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. B
25
8
Commissioning
General
In case of corresponding order the transmitter is ready for
operation after mounting and installation of the connections.
The parameters are set at the factory.
The connected lines must be checked for firm seating. Only
firmly seated lines ensure full functionality.
Checks prior to commissioning
The following points must be checked before commissioning the
device:
• Correct wiring in accordance with
Electrical connections
on page 17.
• The
ambient
conditions
must correspond to the
information given on the name plate and in the data
sheet.
Communication
Note
The HART protocol is not secure, as such the intended
application should be assessed to ensure that these protocols
are suitable before implementation.
Communication with the transmitter takes place using the HART
protocol. The communication signal is modulated onto both
wires of the signal line in accordance with the HART FSK ‘Physical
Layer’ specification.
The HART modem is connected at the signal line of the current
output via which power is also supplied via the power supply
unit.
The device is listed with the FieldComm Group.
1
Transmitter
2
Handheld terminal
3
HART® modem
4
PC with Asset Management Tool
5
Grounding (optional)
6
Power supply unit
(process interface)
R
B
load resistance
(if necessary)
Figure 24: Example for HART connection
Manufacturer ID
0x1A
Device Type ID
0x0D
Profile HART®
5.1
Configuration
DTM, EDD, FDI (FIM)
Transmission signal
BELL Standard 202
Operating modes
• Point-to-point
communication mode –
standard (general address 0)
• Multidrop mode (addressing 1 to 15)
• Burst
Mode
Diagnosis notice
• Overrange / underrange in accordance with NE 43
• HART®
diagnosis