30
TTF200
FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF200-EN REV. A
9.1
Possible HART error messages
Range Displays
the
device
status
Displays
the DIAG.
NO.
Cause Remedy
Electronics
F
1
Device defective
Replace the device
Electronics
S
2
Ambient temperature overshot /
undershot
Check environment; reposition measuring
point if required
Electronics
F
3
EEPROM defective
Replace the device
Electronics M
4
Electronics
overload
Factory
reset
Electronics
F
5
Memory error
Factory reset
Electronics
I
7
LCD display connected
Status info; not an error
Installation /
Configuration
I
8
Device write-protected
Status info; not an error
Electronics
I
9
EEPROM busy
Status info; not an error
Electronics
F
12
Sensor input defective (communication)
Replace the device
Electronics
F
13
Sensor input defective (error)
Replace the device
Electronics
F
14
Sensor input defective (ADC error)
Replace the device
Installation /
Configuration
C
32
Diagnostics simulation mode
Not an error, diagnostic info, measurement
OK
Sensor
F
34
Measuring error, sensor
Check sensor connection
Sensor
F
35
Short-circuit, sensor
Check sensor connection
Sensor
F
36
Wire break, sensor
Check sensor connection
Sensor
F
37
Range overshot, sensor
Check measuring limits
Sensor
F
38
Range undershot, sensor
Check measuring limits
Installation /
Configuration
I
41
Single-point adjustment active, sensor
Status info; not an error
Installation /
Configuration
I
42
Two-point adjustment active, sensor
Status info; not an error
Installation /
Configuration
F
65
Configuration defective
Check configuration:
A) Wrong device
B) Span is too small
C) Incorrect configuration data
Installation /
Configuration
C
71
Reconfiguration is running
Status info; not an error
Operating conditions
F
72
Error in the application
Check configuration, connections; reset to
factory settings
Installation /
Configuration
I
74
Analog output adjustment active
Status info; not an error
Installation /
Configuration
C
75
Analog output in simulation
Status info; not an error
Operating conditions
S
76
Values overshot
Check parameters:
A) Sensor limits overshot
B) Span is too small
NOTICE
If the remedial measures listed for the error message do not improve the status of the device, please consult ABB Service.
Change from one to two columns