Construction sites

Continuously switching of the mains power supply that is connected to emergency light fittings during the construction 
phase of an installation will cause these fittings to discharge and charge their batteries many times over a short period; 
this can shorten the life of the battery and will also result in shortened emergency lamp life. ABB does not recommend 
such practices and may not honour the warranty on batteries when they are subjected to such harsh operating 
conditions. Emergency light fittings are designed to be discharge tested once every 6 months as per AS/NZS2293.2, 
subjecting the product to repeated discharge or charge cycles is regarded as an abuse of the fittings.

Trouble shooting guide

If you have installed and connected the unit as per the instructions listed earlier and it does not function correctly, use the 
following table as a guide to fixing the problem. Look up the type of fault in the left column and check the possible causes 
from the right column.

If the unit still does not work after checking these possible causes, contact ABB service in Australia on 1300 666 595, 
Monday to Friday, 7.00am to 5.00pm (AEST) and ask for help. Our trained service personnel will usually be able to 
take your call immediately and assist you in resolving your difficulty. ABB is committed to providing valuable through-life 
support for its products. 

Doc no. 29-01039

Power pack T8
Nexus LX

Installation manual

Congratulations

Congratulations on choosing to use this ABB product covered by our unique through-life support system. This document 
is designed to assist you during the installation of this product; for the safety of yourself and others 

ABB recommends 

that you read this document thoroughly before commencing installation

. The fittings are designed for easy 

installation. They are advanced pieces of electronic equipment which, when treated with care and maintained through 
regular and appropriate servicing, will perform reliably for many years to come.

Safety warning

In Australia and New Zealand, only licensed electricians are permitted by law to work with 240 volt electrical installations.
Do not attempt to install or connect this product unless you are a licensed electrician.
Turn off and isolate the electrical supply before connecting this fitting to the building wires.
Do not touch the terminals of the terminal block when the light fitting is energised.
The only user-serviceable part is the battery.
Do not tamper with the fitting or the warranty will be void.
As the installer, it is your responsibility to ensure compliance with all relevant building and safety codes, (ie: AS3000,  
AS/NZS2293). Refer to the applicable standards for data and mains cabling installation procedures and requirements.

Important note: This product is designed for indoor use only.

EMC warning

Power pack complies with EMC regulations. We advise that if you incorporate this pack into your product (batten/fitting) 
you must test the complete (product/fitting) for EMC compliance.

PL lamp warning

For PL lamp application it is recommended that the power pack be used without a LDR. The unit should be designated 
as a non-maintained unit. The LDR is not designed to be affixed to a PL lamp. If AC lamp monitoring is required then the 
LDR must be mounted adjacent to the PL lamp. Please contact ABB support centre on 1300 666 595 if you require more 
information. Specific PL lamp power packs are supplied without an LDR and are programmed as non-maintained.

Nexus LX (data cable system)

The Nexus

®

 range of emergency light fitting are designed to be connected together into a special communication network 

over a Level 4 (or higher) high speed, single twisted pair data cable. The Nexus user and technical guide describes all 
you need to know to successfully install a Nexus project. Ask for it from your supervisor, from your employer or from your 
nearest ABB product supplier. The network cabling of the building must be installed as per the procedure detailed in the 
Nexus user and technical guide. No mains or mains carrying cables are to be connected to the data terminals or cables.

This document covers

What’s inside the box

Safety warning

Power pack T8 Nexus LX

Installation instructions

Installation manual

Removal instructions

Warranty information

Testing precautions

Trouble shooting guide

No.

Fault

Possible causes

1

LED not lit; or
LED not flashing green

AC supply not connected; or
AC supply turned off

2

LED is flashing green but AC lamp does not come on when 
connected to mains

Switch active supply turned off; or
Missing loop from unswitched to switched active; or
Lamp damaged; or
Lamp not inserted properly

3

LED is flashing green but lamp does not come on when test 
switch is pressed

Lamp damaged or lamp not inserted properly; or
Battery pack not connected; or
Battery pack damaged; or
Test switch damaged

4

LED not red after the commissioning

Battery pack not connected; or 
LED wire not properly inserted into the terminal block

5

Lamp is lit momentarily when test switch is pressed; or
when mains fail

Battery not fully charged (allow up to 24 hours); or
Battery pack damaged

6

LED is constant green

Unit self checks fail - return to manufacturer

7

Unit LED is not flashing yellow/orange under wink node command

Unit is not receiving communication signal. Check data cable 
wiring path and cable connections. Refer to Nexus user and 
technical guide.