background image

 

 

 

 

2TLC172125M0201, rev. A 

11 

www.abb.com/lowvoltage 

2011-09-20 

6  Technical data 

Manufacturer 

Address 

ABB AB / JOKAB SAFETY 
Varlabergsvägen 11 
SE-434 39 Kungsbacka 
Sweden 

Article number/Ordering data 

Tina 3A: 2TLA020054R0200 
Tina 3Aps: 2TLA020054R1400 

 

Power supply 

Operating voltage 

24 VDC +15 %, -25 % 

Total current consumption 

17 mA (27 mA with max information output) 
Information output: Max 10 mA 

Time delay t (in/out) 

t < 70 µs 

Current through safety device contacts 

12 mA 

Short circuit current between contacts 

10 mA 

Voltage supply at normal operation (protection OK) 
and 24 VDC supply voltage 

Dynamic input: between 9 and 13 volt (RMS) 
Dynamic output: between 9 and 13 volt (RMS) 
Information output: ~ 23 VDC 

 

General 

Protection class 

IP67 

Ambient temperature 

Storage: -30…+70°C 
Operation: -10…+55°C 

Humidity range 

35 to 85 % (with no icing or condensation) 

Housing material 

PVC 

Connectors 

M12 5-pole connector 
Green loop wires (A1 & A2) 
Orange loop wires (B1 & B2) 
Brown (+24 VDC), Blue (0 VDC) wires (Tina 3Aps only) 

Size 

56 x 27 x 24 (L x W x H) 

Weight 

~ 30 g 

Colour 

Black 

 

Safety / Harmonized Standards 

Conformity 

European Machinery Directive 2006/42/EC 

 

EN ISO 12100-1:2003, EN ISO 12100-2:2003, 
EN 60204-1:2007, EN 954-1:1996, EN ISO 13849-1:2008, 
EN 62061:2005 

IEC/EN 61508-1…7 

SIL3, PFH

d

: 4.50*10

-9

 

EN 62061 

SIL3 

EN ISO 13849-1 

Performance level: Pl e, category 4 

EN 954-1 

Category 4 

Certificates 

TÜV Nord 

Summary of Contents for Tina 3A/Aps

Page 1: ...ABB AB Jokab Safety Varlabergsvägen 11 SE 434 39 Kungsbacka Sweden www abb com lowvoltage Original instructions Tina 3A Aps Adaptor unit ...

Page 2: ...AFETY will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product machine system or other application or use The following are some examples of applications for which particular attenti...

Page 3: ...iew 5 General description 5 Safety regulations 5 3 Connections 6 Connection examples 7 4 Installation and maintenance 9 Installation precautions 9 Maintenance 9 Testing of the safety functions 9 Troubleshooting 9 5 Operation 10 LED indication 10 Information output signal attributes 10 6 Technical data 11 Dimensions 12 7 EC Declaration of conformity 13 ...

Page 4: ...r of this document has knowledge of the following Basic knowledge of ABB Jokab Safety products Knowledge of machine safety Special notes Pay attention to the following special notes in the document Warning Danger of severe personal injury An instruction or procedure which if not carried out correctly may result in injury to the technician or other personnel Caution Danger of damage to the equipmen...

Page 5: ...quipped with two additional connection cables for external power supply The Tina3A Aps adaptor unit is intended for use in safety circuits in accordance with EN 60204 1 Warning In order to maintain the highest safety level and reduce the risk of electrical interference the unit must be installed within the same physical encapsulation as the safety device The connection cables should be as short as...

Page 6: ...ot monitored and must therefore be installed within the same physical enclosure as the safety device to maintain the highest safety level fault exclusion refer to EN ISO 13849 2 2003 Annex D The safety loops shall not be used for purposes other than intended All loading or tampering with loops can lead to serious risk of life 5 pole M12 connector 1 Brown 24 VDC 2 White Dynamic signal input 3 Blue ...

Page 7: ...2TLC172125M0201 rev A 7 www abb com lowvoltage 2011 09 20 Connection examples Tina 3A Caution All cable colours according to ABB Jokab Safety standard cables ...

Page 8: ...2TLC172125M0201 rev A 8 www abb com lowvoltage 2011 09 20 Tina 3Aps Caution All cable colours according to ABB Jokab Safety standard cables ...

Page 9: ...s unit The LED should flash between green and red Interrupt protection The LED should light red The LED should light green when protection is OK and if the safety circuit s before this unit is not interrupted Troubleshooting LED indication Expected causes of faults Checking and measures to take Lights red Sensor pushed opened Check status of the sensor Bad connection between loops green and or ora...

Page 10: ...l is applied high H 0 VDC The pin is connected to 0 VDC low L The information output signal depends on the input signal according to the table below Note that if the safety is interrupted the information output signal is always low L Input signal pin 2 Dynamic signal No dynamic signal 24 VDC 0 VDC Info output signal pin 5 High High Low High The delay for switching the information signal output fro...

Page 11: ...tage Dynamic input between 9 and 13 volt RMS Dynamic output between 9 and 13 volt RMS Information output 23 VDC General Protection class IP67 Ambient temperature Storage 30 70 C Operation 10 55 C Humidity range 35 to 85 with no icing or condensation Housing material PVC Connectors M12 5 pole connector Green loop wires A1 A2 Orange loop wires B1 B2 Brown 24 VDC Blue 0 VDC wires Tina 3Aps only Size ...

Page 12: ...2TLC172125M0201 rev A 12 www abb com lowvoltage 2011 09 20 Dimensions Tina 3A Tina 3Aps NB All measurements in millimetres ...

Page 13: ...d to compile the technical file Lars Magnus Felth ABB AB JOKAB SAFETY Varlabergsvägen 11 SE 434 39 Kungsbacka Sweden Product Certificate Serialnumber Non contact safety sensor Eden Adam Eva E C EC 44 207 10 372092 001 000 000 999 999 Adapter unit Tina 1 8 Tina 10 12 44 207 10 372092 001 000 000 999 999 Muting unit FMC Tina 44 207 10 372092 001 000 000 999 999 Non contact safety sensor including lo...

Reviews: