Appendix C – Pedestal requirements
Any pedestal solution designed for Terra DC Wallbox needs to fulfill the specific ISO standards for civil contruc-
tions (note: specific local regulations may apply).
Additionally, whereas no specific contraint is provided by local regulations, the minimum set of requirements
necessary to provide a safe installation are listed in the table below to be verified in the temperature range be-
tween -50°C - +60°C:
Minimum Wind load resistance
100km/h
Minimum compression load capability (applied on center of mass of the
WB)
4kN
Side / Back / frontal impact MAX (applied on the pedestal/WB) higher
point
3kN
Pulling /Pushing force applied (to gun holders if they are mechanically con-
nected to same stucture and external to the WB area)
3kN
Min / Max distance of gun holder from WB (if mechanically connected to
pedestal structure)
300mm / 1000mm
Rust protection paint
Yes
Minimum clearance areas side / top / bottom around the charger
300mm
Recommended foundation requirements (min tilting torque)
To be designed consid-
ering the max admitta-
ble loads in each direc-
tion
Vibration test required on the full system
According to procedure
described in IEC 60068-
2-27: 2008 and IEC
60068-2-6: 2007
Electrical ground connection
To the chassis of the
DCWB