Installation instructions 

 

The installation, commissioning, maintenance and repair of 
devices in potentially explosive atmospheres must only be 
carried out by appropriately trained personnel. Works may be 
carried out only by persons, whose training has included 
instructions on different types of protection and installation 
techniques, concerned rules and regulations as well as general 
principles of zoning. The person must possess the appropriate 
competences for the type of work to be conducted. 
When operating with combustible dusts, comply with 
EN 60079-31. 
The safety instructions for electrical apparatus in potentially 
explosive areas must be in accordance with Directive 
2014/34/EU (ATEX) and IEC 60079-14 (Installation of electrical 
equipment in potentially explosive areas). 
Comply with the applicable regulations for the protection of 
employees to ensure safe operation. 
 

 

Information about opening and closing the housing 

 

 

 DANGER 

Risk of explosion if the device is operated with the housing 
or terminal box open! 

Before opening the housing or the terminal box, note the 
following points:  
•  A valid fire permit must be present. 
•  Make sure that there is no explosion hazard. 
•  Switch off the power supply and wait for t > 4 minutes 

before opening. 

 

 

NOTICE 

Adverse effect on the type of protection 

Damage to the cover thread results in loss of the ‘flameproof 
(enclosure) (Ex d)’ type of protection. 
•  Handle the cover with care. 

 

 

 

 

 

Requirements for operation with the ‘flameproof 
(enclosure)’ (Ex d) type of protection 

Before installation, you must check if  
the I/P signal converter fulfills the measurement and safety 
requirements of the measuring point. 

•  When performing wiring, the parameters in the 

specification and the information in the explosion 
protection certificate must be complied with. 

•  The device may only be operated using instrument air 

that is free from oil, water and dust. Flammable gases, 
oxygen or oxygen-enriched gases must not be used. 

 

 

Cable entries 

 

When operating with the ‘flameproof (enclosure) (Ex d)’ type of 
protection, use only cable glands with the corresponding full ‘Ex 
d’ approval. 

•  Secure all cable entries against twisting and loosening by 

using a medium-strength securing adhesive. 

•  When the I / P signal converter is used at ambient 

temperatures above 60 °C (140 °F) or below –20 °C (–4 °F), 
make sure to use cable entries and cables suitable for an 
operating temperature of up to the maximum ambient 
temperature plus 10 K, or for an operating temperature 
down to the minimum ambient temperature. 

 

 

Operating instructions 

 

Changing the type of protection 

 

The devices can be operated as delivered with either the 
"intrinsically safe (Ex ia)" or "flameproof (enclosure) (Ex d)" types 
of protection. 
A device that has been operated with the "flameproof 
(enclosure) (Ex d)" type of protection must no longer be 
operated with the "intrinsically safe (Ex ia)" type of protection, 
as the electronics may have been damaged. 
For this reason the devices must be permanently marked during 
commissioning (e.g. cross out or mask over "Ex ia"). 
 

 

 

 

Summary of Contents for TEIP11

Page 1: ...P11 PS Introduction I P signal converter for controlling pneumatic actuators or conventional positioners for valve positioning Additional Information Additional documentation on TEIP11 TEIP11 PS is available for download free of charge at www abb com positioners Alternatively simply scan this code ...

Page 2: ...l room housing unit for block mounting 9 Field mount housing 9 4 Product identification 10 Name plate 10 Scope of delivery 10 5 Transport and storage 10 Inspection 10 Storage conditions 10 Returning devices 10 6 Installation 11 Mounting 11 Control room housing unit for rail mounting 11 Control room housing unit for block mounting 11 Aluminum stainless steel field mount housing 12 Field mount housi...

Page 3: ...ns and repairs to the product may only be performed if expressly permitted by these instructions Information and symbols on the product must be observed These may not be removed and must be fully legible at all times The operating company must strictly observe the applicable national regulations relating to the installation function testing repair and maintenance of electrical products Warnings Th...

Page 4: ...id for example for mounting purposes For use as a bracket for external loads for example as a support for piping etc Material application for example by painting over the housing name plate or welding soldering on parts Material removal for example by spot drilling the housing Warranty provisions Using the device in a manner that does not fall within the scope of its intended use disregarding this...

Page 5: ...S Supply pressure 1 4 bar 20 psi 2 5 bar 37 psi Output signal 0 2 to 1 bar 3 to 15 psi 0 4 to 2 bar 6 to 30 psi Valid for Option 509 only increased input signal Thermal data T4 40 C Tamb 85 C T5 40 C Tamb 70 C T6 40 C Tamb 55 C Special conditions The I P signal converter is suited for use in an ambient temperature range of 40 C to maximum 85 C If the I P signal converter is used at an ambient temp...

Page 6: ...set up outdoors as a pneumatic power supply when used with combustible gases The supplied gas must be kept sufficiently free of air and oxygen to prevent a potentially explosive atmosphere from forming The gas must always be routed to the outside FM CSA Intrinsically safe FM FM intrinsically safe not for metal field housing units I S CL I Div 1 Grp A B C D FM intrinsically safe only for metal fiel...

Page 7: ...re Ex d type of protection Handle the cover with care Requirements for operation with the flameproof enclosure Ex d type of protection Before installation you must check if the I P signal converter fulfills the measurement and safety requirements of the measuring point When performing wiring the parameters in the specification and the information in the explosion protection certificate must be com...

Page 8: ...he force changes in proportion to the current input signal flowing through the coil A counterforce is applied on the other side of the lever arm through the dynamic air pressure present at the nozzle and the flapper The force is controlled in such a way that a balance of the two torques is achieved If a torque imbalance occurs the lever arm rotates This rotation changes the air gap between the noz...

Page 9: ...rol room housing unit for block mounting enables you to install a number of converters in a small space This design features central air supply via connection block and stop valves in the air connectors of the integrated signal converter A maximum of 4 signal converters can be fitted on the connection blocks required for block mounting If necessary 2 or 3 or max 4 connection blocks can be connecte...

Page 10: ...ck the devices immediately after unpacking for possible damage that may have occurred from improper transport Details of any damage that has occurred in transit must be recorded on the transport documents All claims for damages must be submitted to the shipper without delay and before installation Storage conditions Bear the following points in mind when storing devices Store the device in its ori...

Page 11: ...lation instructions For mounting rails that are mounted in a vertical position the electrical connection for the device should preferably face to the left For mounting rails that are mounted in a horizontal position the electrical connection for the device should preferably be facing up Control room housing unit for block mounting For this design a special connection block is used to mount the uni...

Page 12: ...1 Terminal for signal input covered 2 Cable entry 3 Supply air connection 4 Output covered Figure 7 Aluminum stainless steel field mount housing Installation instructions Position the housing so that the cable gland is facing downwards or sideways to prevent humidity from penetrating the device Accessories A stainless steel mounting bracket is available as an accessory for installation The mountin...

Page 13: ... devices Do not install the signal line together with power supply leads Cable glands The field mount housings feature a PG 11 cable entry Aluminum or stainless steel field mount housing Ex Protection Cable entry Standard Ex ia Screw connection in NPT Ex d Threaded hole M20 1 5 FM CSA Intrinsically Safe Explosion Proof Threaded hole in NPT Position of the terminals The electrical connection is pro...

Page 14: ...ducer to make sure that the pressure does not go over 4 bar 60 psi even in case of a malfunction Threaded holes or NPT are provided for connecting the air pipes supply air and output pipes The connections for the power supply supply air and the output are marked accordingly Pneumatic data TEIP11 Instrument air Free of oil water and dust acc to DIN ISO 8573 1 Pollution and oil content according to ...

Page 15: ...for the adjustment process Note When using a field mount housing first remove the cover to access the screws 1 Range 2 Zero point Figure 9 Adjusting screws 9 Repair Repair and maintenance activities may only be performed by authorized customer service personnel When replacing or repairing individual components use original spare parts Returning devices Use the original packaging or a secure transp...

Page 16: ...g of them As of 8 15 2018 this product will be under the open scope of the WEEE Directive 2012 19 EU and relevant national laws for example ElektroG Electrical Equipment Act in Germany The product must be supplied to a specialist recycling company Do not use municipal waste collection points These may be used for privately used products only in accordance with WEEE Directive 2012 19 EU If there is...

Page 17: ...or Customer details Company Address Contact person Telephone Fax Email Device details Type Serial no Reason for the return description of the defect Was this device used in conjunction with substances which pose a threat or risk to health Yes No If yes which type of contamination please place an X next to the applicable items biological corrosive irritating combustible highly extremely combustible...

Page 18: ...18 TEIP11 TEIP11 PS I P SIGNAL CONVERTER OI TEIP11 TEIP11 PS EN REV M 12 Appendix Control Document Connection diagram 900842 FM ...

Page 19: ...TEIP11 TEIP11 PS I P SIGNAL CONVERTER OI TEIP11 TEIP11 PS EN REV M 19 ...

Page 20: ...20 TEIP11 TEIP11 PS I P SIGNAL CONVERTER OI TEIP11 TEIP11 PS EN REV M 12 Appendix Control Document Connection diagram 900842 CSA ...

Page 21: ...TEIP11 TEIP11 PS I P SIGNAL CONVERTER OI TEIP11 TEIP11 PS EN REV M 21 ...

Page 22: ...22 TEIP11 TEIP11 PS I P SIGNAL CONVERTER OI TEIP11 TEIP11 PS EN REV M Notes ...

Page 23: ...TEIP11 TEIP11 PS I P SIGNAL CONVERTER OI TEIP11 TEIP11 PS EN REV M 23 Notes ...

Page 24: ...11 TEIP11 PS EN Rev M 08 2018 We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illus...

Reviews: