19
7
MODBUS REGISTRATIONS…
Continued…
Register Number
Read/Write
Description
Response Entry
Analog Inputs
001
R
Analog Input A1
002
R
Analog Input A2
003
R
Analog Input A3
004
R
Analog Input A4
005
R
Analog Input A5
0 to 4095 (0 to 100% input range)
006
R
Analog Input A6
007
R
Analog Input B1
Value =
Response x (FS – Z)
008
R
Analog Input B2
4095
009
R
Analog Input B3
010
R
Analog Input B4
011
R
Analog Input B5
012
R
Analog Input B6
+ Z
Where FS = Engineering range Full Scale
for the appropriate input
Z
= Engineering range Zero for
the appropriate input
Input Number
Read/Write
Description
Response Entry
Logic Equation Result State
071
R
Logic Equation 1 Result
072
R
Logic Equation 2 Result
073
R
Logic Equation 3 Result
074
R
Logic Equation 4 Result
075
R
Logic Equation 5 Result
0 = Inactive
076
R
Logic Equation 6 Result
1 = Active
077
R
Logic Equation 7 Result
078
R
Logic Equation 8 Result
079
R
Logic Equation 9 Result
080
R
Logic Equation 10 Result
Instrument Status
091
R
Recording Stopped
0 = Recording
1 = Recording Stopped
092
R
Paper Out State
0 = Paper Available
1 = Less Than 0.5m of Paper
093
R
Line (Power) Failure State
0 = Inactive, 1 = Fail
…7.2
Inputs
7.3
Input Registers