21
Data
Code
Data
Values
direct.
Remotely set start value of stage I>
S31
R
0.5...2.5 x I
n
Remotely set operation time value
S32
R
0.05...100 s
or time multiplier of stage I>
0.05...1.00
Remotely set start value of stage I>>
S33
R
0.5...20 x I
n
999 =
∞
, infinite
Remotely set operation time value
S34
R
0.04...100 s
of stage I>>
Remotely set checksum of switch-
S35
R
0...255
group SG1
Max. measured current or current
V1
R
0...63 x I
n
value at relay operation
Number of starts of stage I>
V2
R
0...255
Number of starts of stage I>>
V3
R
0...255
Duration of the latest start
V4
R
0...100%
situation of stage I>
Duration of the latest start
V5
R
0...100%
situation of stage I>>
Phase data recorded at the
V6
R
1 = I
L3
>, 2 = I
L2
>, 4 = I
L1
>,
latest triping occasion
16 = I
L3
>>, 32 = I
L2
>>,
64 = I
L1
>> + combinations
Current value at relay operation
V7
R
0…63 x I
n
Resetting of output relays and
V101
W
1 = output relays and operation
operation indicators
indicators are reset
Resetting of output relays and
V102
W
1 = output relays and operation
operation indicators and erasing
indicators are reset and
of recorded data
registers (codes V1...V7)
are erased
Remote control of settings
V150
R, W
0 = setting with knobs S11...S15
alerted
1 = remote settings S31...S35
alerted
Event mask word
V155
R, W
0...255, see paragraph
"Event codes"
Manual or automatic resetting of
V156
R, W
0…15, see paragraph
LED indicators (SG2)
"Selector switches"
Programming push-buttons
V157
R, W
0…7
Opening of password for remote
V160
W
1...999
setting of module parameters
Renaming or closing of password
V161
W
0...999
for remote setting of parameters
Activation of the self-supervision
V165
W
1 = self-supervision output is
system output
activated and IRF indicator
turns on in about 5 seconds,
whereafter the self-supervi-
sion system and the IRF
indicator reset.
Fault code number
V169