11
Switchgroup SGF6
Selection of the output signal controlling the
TRIP indicator on the front panel. When the
switch linked to a certain signal is in position 1,
the TRIP indicator is lit once the signal is acti-
vated. At the same time the concerned signal
starts the recovery function, provided the recov-
ery output is in use (selected with SGR9/_ ).
Switch
Function
Factory
setting
SGF6/1
The SS1 signal activates the TRIP indicator and starts the recovery
0
function.
SGF6/2
The TS1 signal activates the TRIP indicator and starts the recovery
1
function.
SGF6/3
The SS2 signal activates the TRIP indicator and starts the recovery
0
function.
SGF6/4
The TS2 signal activates the TRIP indicator and starts the recovery
1
function.
SGF6/5
The SS3 signal activates the TRIP indicator and starts the recovery
0
function.
SGF6/6
The TS3 signal activates the TRIP indicator and starts the recovery
0
function.
SGF6/7
The SS4 signal activates the TRIP indicator and starts the recovery
0
function.
SGF6/8
The TS4 signal activates the TRIP indicator and starts the recovery
0
function.
∑
SGF6
10
Switchgroup SGF7
The switchgroup SGF7 is used for selecting the
rated voltage of the relay module.
Switch
Rated voltage
Factory
100 V
110 V
115 V
120 V
setting
SGF7/1
0
1
0
1
0
SGF7/2
0
0
1
1
0
SGF7/3
When the switch is in position 1,
0
the selected rated voltage is divided by
√
3.
Then the following voltages are received:
57.7 V
63.5 V
66.4 V
69.3 V
SGF7/4...8
Not in use
0
∑
SGF7
0