31
Data
Channel Code
Data
Values
direction
Interlocking and Conditional Direct
0
M200 RW(e)
Commands =
Output Control program
:
LOAD, LOADN
(format; operation, operand)
M300
AND, ANDN
OR, ORN
OUT
END
Interlocking variables =
status closed (1...3)
or active (4...13)
status undefined
(101...103)
status open (201...203)
Output code (20, 21)
Special register (60, 61)
L/R key switch position
information (62)
Memory No. (70...89)
Variables for Conditional
Direct Output Control =
status closed (1...3) or
active (4...13)
status undefined
(101...103)
status open (201...203)
Output code (22...25,
220 or 221)
Special register (60, 61)
L/R key switch
position (62)
Memory No. (70...89)
Event delay; —>10 (open)
1...3
S10
RW(e)
0.00, or 0.02...60.00 s
Event delay; —>01 (close)
1...3
S11
RW(e)
0.00, or 0.02...60.00 s
Event delay; —>11 (undefined)
1...3
S12
RW(e)
0.00, or 0.02...60.00 s
Event delay; —>00 (undefined)
1...3
S13
RW(e)
0.00, or 0.02...60.00 s
Use of input 7
7
S1
RW(e)
0 = general mode
1 = pulse counter without
indication
2 = pulse counter with
indication
Operation principle of input
4...13
S2
RW(e)
0 = active at low state
channels 4...13
1 = active at high state
Signal output activation via
4...13
S3
RW(e)
0 = no SIGNAL output
input channels 4...13
activated
22 = SIGNAL1 output
activated
23 = SIGNAL2 output
activated
24 = SIGNAL3 output
activated
25 = SIGNAL4 output
activated